RS232 Communications Protocol & Command Set (continued)
Non Critical Load Outlets On
This command controls the relay that feeds power to the NCL Outlets. Note that if the MAIN relay is off, the outlets will still be
Send to UPS: | NCL_ON<CR> | |
Action: | NCL relay closes. | |
Response from UPS: | NCL_OUTLETS_ON<CR> (if MAIN | |
| relay is ON) | |
| NCL_OUTLETS_OFF<CR> (if MAIN | |
| relay is OFF) | |
Non Critical Outlets Off |
| |
NCL_OFF<CR> | ||
Send to UPS: | ||
Action: | NCL relay opens. | |
Response from UPS: | NCL_OUTLETS_OFF<CR> |
Set Low Battery NCL (Non-Critical Load) Shutoff
It is desirable to allow the user to set the battery storage threshold in which the
A common example of critical equipment would be a projector. It is critical that power be maintained to a projector to allow its fan to run and cool the bulb. If the bulb is allowed to overheat, it will be damaged and is very expensive to replace.
Send to UPS: | BATTHRESH<SP>XX<CR> |
| <SP> represents a space: 20 Hex |
| XX is a number between 25 and 60 |
| represented in ASCII. |
If XX is a valid number, between 25 and 60:
Action:Assigns the battery threshold variable with the value XX
Response from UPS: | BTHRESH<SP>XX<CR> |
If XX is not valid: |
|
Action: | None |
Response from UPS: | INVALIDCMD<CR> |
Enable Audible Alarm
It is important that the UPS be as quiet as possible as it will be located in a home theater environment. It is desirable to control the warning beeper. The default setting for the alarm is OFF.
Send to UPS: | BEEPON<CR> | ||
Action: | The beeper will sound when running | ||
|
| from battery. | |
Response from UPS: | BEEPISON<CR> | ||
Disable Warning Beeper |
|
| |
Send to UPS: | BEEPOFF<CR> | ||
Action: | The beeper will not sound when running | ||
|
| from battery. | |
Response from UPS: | BEEPISOFF<CR> | ||
Restore Default Settings |
| ||
RESTORE<CR> | |||
Send to UPS: | |||
Action: | Set | ||
|
| to 66% | |
|
| Disable the warning beeper (2.7) | |
|
| Set High Voltage Failure Threshold to | |
|
| 147V (2.8) | |
|
| Set Low Voltage Failure Threshold to | |
|
| 88V (2.9) | |
|
| Set Battery Mode Voltage to 120V (2.10) | |
Response from UPS: | DEFAULTSRESTORED<CR> |
QUERIES
Request Outlet Status
Transmit the ON/OFF status of the outlet banks.
Send to UPS: | ?OUTLETSTAT<CR> |
If NCL Outlets are ON: |
|
Response from UPS: | NCL_OUTLETS_ON<CR> |
If NCL Outlets are OFF: |
|
Response from UPS: | NCL_OUTLETS_OFF<CR> |
If CL Outlets are ON: |
|
Response from UPS: | CL_OUTLETS_ON<CR> |
If CL Outlets are OFF: |
|
Response from UPS: | CL_OUTLETS_OFF<CR> |