RS232 Communications Protocol & Command Set (continued)

Responses and Warning Messages

A warning message is to be transmitted whenever the status of the fol- lowing systems changes:

Outlet Bank Status Messages

Whenever an outlet bank switches state (ON or OFF) the UPS sends a message to the controller:

Condition

Response from UPS

 

 

CL Outlet Bank switches ON

CL_OUTLETS_ON<CR>

 

 

CL Outlet Bank switches OFF

CL_OUTLETS_OFF<CR>

 

 

NCL Outlet Bank switches ON

NCL_OUTLETS_ON<CR>

 

 

NCL Outlet Bank switches OFF

NCL_OUTLETS _OFF<CR>

 

 

Power Status Messages

Whenever the power changes state the UPS sends a message to the controller:

Condition

Response from UPS

 

 

UPS is not in AVR or BATTERY

NORMAL<CR>

mode

 

 

 

UPS is in AVR boosting 13%

AVRBOOST1<CR>

 

 

UPS is in AVR boosting 26%

AVRBOOST2<CR>

 

 

UPS is in AVR bucking 15%

AVRBUCK1<CR>

 

 

UPS is in BATTERY mode

BATTERY<CR>

 

 

Battery charge falls below critical

LOWBATT<CR>

load threshold

 

 

 

Input voltage exceeds high volt-

OVERVOLTAGE<CR>

age failure t’hold

 

 

 

Input voltage falls below low

UNDERVOLTAGE<CR>

voltage failure t’hold

 

 

 

Battery charge falls below critical

LOWBATT<CR>

load threshold

 

 

 

Invalid Command or Query

If the UPS receives a command or query ASCII string that it does not understand, an error message is transmitted.

Condition:

Command or query not recognized or

 

properly formatted

Response from UPS:

INVALIDCMD<CR>

16

 

USA & Canada (800) 472-5555 • (707) 283-5900 • Fax (707) 283-5901

Image 18
Contents MAX Home Cinema UPS Table of Contents Before You BeginImportant Safety Instructions Model # M1500-UPSBasic Operation Installing Your UPSHardware Installation Guide Front Panel DescriptionFront Panel Display LED Descriptions Rear Panel DescriptionAdvanced Operation LED Color StatusRS232 Control with Open Protocol Home Cinema Power Control SoftwareSoftware Installation For Windows XP Home and Professional For Windows 95/98/MeFor Windows For Windows NTHome Cinema Power Control Software Instructions Main MenuOverview Setup Menu Main Window DescriptionsAdvanced Setup Menu Battery Replacement Battery FeaturesTesting The Battery Backup Function LOG MenuDiagnostics Battery Replacement ProcedureRemove the four retaining screws Troubleshooting Technical SpecificationsProblem Possible Cause Solution Main Power On RS232 Communications Protocol & Command SetController Commands Communications ProtocolNon Critical Load Outlets On Set Low Battery NCL Non-Critical Load ShutoffEnable Audible Alarm Request Outlet StatusRequest Output Voltage Status Request Battery Charge Level StatusRequest Input Voltage Level Request Load Level StatusResponses and Warning Messages Outlet Bank Status Messages Power Status MessagesInvalid Command or Query Condition Response from UPSUpgrade Policy FCC Notice and WarrantiesFCC Notice INS0763 REV. B 7/05