Panamax M1500-UPS Request Input Voltage Level, Request Output Voltage Status, Identify Equipment

Page 17

RS232 Communications Protocol & Command Set (continued)

Request Input Voltage Level

Transmit the input AC voltage status

Send to UPS:

?INPUTVOLTS<CR>

Response from UPS:

XXX<SP>VAC<SP>IN<CR>

 

XXX is the input AC voltage represented

 

in ASCII.

Request Output Voltage Status

Transmit the output voltage state

Send to UPS:

?OUTPUTSTAT

Response from UPS:

XXX<SP>VAC<SP>OUT<CR>

 

XXX is the output voltage represented

 

in ASCII.

If the UPS is not in AVR or BATTERY mode:

Response from UPS: NORMAL<CR>

If the UPS is in AVR mode and boosting voltage by 13%

Response from UPS: AVRBOOST1<CR>

If the UPS is in AVR mode and boosting voltage by 26%

Response from UPS: AVRBOOST2<CR>

If the UPS is in AVR mode and bucking voltage by 11%

Response from UPS:

AVRBUCK1<CR>

If the UPS is in BATTERY mode

Response from UPS:

BATTERY<CR>

Request Load Level Status

Transmit the load level percentage.

Send to UPS:

?LOADSTAT<CR>

Response from UPS:

XX<SP>%LOAD<CR>

 

XX is the load percentage represented

 

in ASCII.

Request Battery Charge Level Status

Transmit the remaining battery charge percentage.

Send to UPS:

?BATTERYSTAT<CR>

Response from UPS:

XX<SP>%BATTERY<CR>

 

XX is the battery charge percentage

 

represented in ASCII.

Identify Equipment

Transmit the model number, firmware number and revision.

Send to UPS:

?ID<CR>

Response from UPS:

PANAMAX<CR>

 

M1500-UPS<CR>

 

FW<SP>PARTNUMBER<CR>

 

REV<SP>REVISION<CR>

List all Commands and Queries

 

 

Send to UPS:

HELP<CR>

Response from UPS:

MAIN_ON<CR>

 

MAIN_OFF<CR>

 

NCL_ON<CR>

NCL_OFF<CR>

BATTHRESH<CR>

BEEPON<CR>

BEEPOFF<CR>

RESTORE<CR>

?OUTLETSTAT<CR>

?INPUTVOLTS<CR>

?OUTPUTSTAT

?LOADSTAT<CR>

?BATTERYSTAT<CR>

?ID<CR>

HELP<CR>

USA & Canada (800) 472-5555 • (707) 283-5900 • Fax (707) 283-5901

 

15

Image 17
Contents MAX Home Cinema UPS Before You Begin Table of ContentsModel # M1500-UPS Important Safety InstructionsHardware Installation Guide Installing Your UPSBasic Operation Front Panel DescriptionRear Panel Description Front Panel Display LED DescriptionsLED Color Status Advanced OperationSoftware Installation For Windows XP Home and Professional Home Cinema Power Control SoftwareRS232 Control with Open Protocol For Windows 95/98/MeFor Windows NT For WindowsOverview Home Cinema Power Control Software InstructionsMain Menu Main Window Descriptions Setup MenuAdvanced Setup Menu Testing The Battery Backup Function Battery FeaturesBattery Replacement LOG MenuRemove the four retaining screws DiagnosticsBattery Replacement Procedure Problem Possible Cause Solution TroubleshootingTechnical Specifications Controller Commands RS232 Communications Protocol & Command SetMain Power On Communications ProtocolEnable Audible Alarm Set Low Battery NCL Non-Critical Load ShutoffNon Critical Load Outlets On Request Outlet StatusRequest Input Voltage Level Request Battery Charge Level StatusRequest Output Voltage Status Request Load Level StatusInvalid Command or Query Power Status MessagesResponses and Warning Messages Outlet Bank Status Messages Condition Response from UPSFCC Notice Upgrade PolicyFCC Notice and Warranties INS0763 REV. B 7/05