How to Recover From a Lost Password

You can use a local computer that connects to the Switched Rack PDU through the serial port on the front of the unit.

1.Select a serial port at a local computer, and disable any service that uses the port.

2.Use the configuration cable (940-0144) to connect the selected port to the serial port on the front panel of the PDU.

3.Run a terminal program (such as HyperTerminal) and configure the selected port for 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control, and save the changes.

4.Press ENTER to display the User Name prompt.

5.Press the Reset button on the Switched Rack PDU, which causes the Switched Rack PDU to restart, a process that typically takes approximately 15 seconds.

6.Press ENTER as many times as necessary to redisplay the User Name prompt, then use apc for the user name and password. (If you take longer than 30 seconds to log on after the User Name prompt is redisplayed, you must start the login procedure again at step 4.)

7.From the Control Console menu, select System, then User Manager.

8.Select Administrator, and change the User Name and Password settings, both of which are now defined as apc.

9.Press CTRL-Cand log off.

Reconnect any cable that you disconnected in step 2 and restart any service that you disabled in step 1.

Note

Switched Rack PDU Installation and Quick-Start Manual

13

Image 17
Contents Switched Rack Power Distribution Unit Page Contents How to Download Firmware Updates Warranty and Service Preliminary Information Documentation AdditionalInventory Receiving inspectionInstallation guidelines Install the Switched Rack PDUHow to attach cords to the tray Attach the cordInstall the Switched Rack PDU Connection procedures Install using the rubberFeet provided Placing one in each cornerOverview TCP/IP configuration methods Quick ConfigurationPassword to access the Switched Rack PDU through Option enabled, you can use apc for both the user nameConfiguration Bootp the default settingSee also section in the Addendum Option 43 = 01 04 31 41 50 43 where Control console Local access toRemote access to If you are not using a Bootp or Dhcp server to configure Control console on page 10 or Remote access to the controlWill take effect when you log out If you disconnected a cable during the procedureTelnet OverviewWeb interface How to Recover From a Lost Password Xmodem How to Download Firmware UpdatesLimited warranty Warranty and ServiceWarranty limitations Obtaining serviceGeneral policy Life-Support PolicyExamples of life-support DevicesPage Page Radio Frequency Interference APC Worldwide Customer Support