MX28B-PDF Product Manual

3.1.6 Mounting

The box frame housing is self-supporting, but designed to be bolted to the floor of the housing structure. The figure below shows the footprint of the box frame and the mounting points with dimensions (shown in inches). Consult the system design specifications to see if it is necessary to electrically isolate the frame from the floor structure. This is required in many installations. Insulator kit, part number AAB-0597 is available if required.

23.0

1.50

 

FRONT

11.5

11.5

Figure 3-1 Mounting diagram

3.2 INPUT POWER CONNECTIONS

The PDF –48VDC input bus offers multiple connection points for both 1 inch or 1.75 inch on center lugs. The +48VDC return bus has connection points at both the top and bottom for 1 inch and 1.75 inch lugs. If splice plates are used, they also are configured with holes for connection.

3.3 DC SYSTEM GROUNDING

THE POSITIVE LOAD CONNECTION (RETURN BUS) FOR THE POWER DISTRIBUTION FRAME MUST BE CONNECTED TO THE FACILITY MASTER STATION GROUND. DETAILS FOR THIS CONNECTION SHOULD BE PROVIDED IN THE SITE ELECTRICAL GROUNDING PLANS.

APC

11

Image 11
Contents Power Distribution Frame Revision Date Description Table of Contents General PrecautionsGeneral Information Introduction Inspection Upon Receipt of GoodsReturn of Damaged Goods Concealed DamageSystem Configurations Circuit Breakers Input -48 VDC Bus60A 70A 80A 100A Indicators and AlarmsEnvironmental Mechanical SpecificationsEquipment Inspection Installation Procedures PreparationRecommended Tools Recommended Test EquipmentMounting Mounting diagramWith splice plates Without splice plates Circuit Breaker InstallationLoad connections Load ConnectionsWarranty Returns Customer Service and SupportWarranty Provisions General Provisions Exclusions and Limitations Warranty Repair or Replacement