American Power Conversion MX28B-PDF manual Input -48 VDC Bus, Circuit Breakers

Page 7

Revision A

MX28B-PDF Product Manual

2.2.1 Input –48 VDC Bus

All six busses can be isolated, or tied together with splice plates depending on customer desires.

Splice Plates

Installed

Without Splice

Plates

Figure 2-2 Bus Bars

2.2.2 Circuit Breaker Tiers

Each circuit breaker tier provides positions for mounting 24 plug-in circuit breakers. Each tier bus is connected to the –48 VDC input bus with each side having an ampacity of 600 amperes.

2.2.3 Circuit Breakers

The PDF utilizes plug-in magnetic circuit breakers to supply loads from the –48 VDC bus. Each circuit breaker has auxiliary contacts that close if the breaker trips, thus enabling monitoring of fault conditions. Circuit breakers are available with ratings from 1 – 100 amperes (see Table 2-1)

Plug-in circuit breakers rated at 60A or more require two mounting positions. They are available in kit form (see kit selection information in Table 2-2). These kits include the breaker and all necessary mounting hardware.

APC

7

Image 7
Contents Power Distribution Frame Revision Date Description Table of Contents General PrecautionsGeneral Information Introduction Inspection Upon Receipt of GoodsReturn of Damaged Goods Concealed DamageSystem Configurations Circuit Breakers Input -48 VDC Bus60A 70A 80A 100A Indicators and AlarmsEnvironmental Mechanical SpecificationsEquipment Inspection Installation Procedures PreparationRecommended Tools Recommended Test EquipmentMounting Mounting diagramWith splice plates Without splice plates Circuit Breaker InstallationLoad connections Load ConnectionsWarranty Provisions General Provisions Customer Service and SupportWarranty Returns Exclusions and Limitations Warranty Repair or Replacement