Page 12

MX28B-PDF Product Manual

Revision A

+48V Bus

-48V Bus without

splice plate

-48V Bus

Splice plate

With splice plates

without splice plates

Figure 3-2 Bus Bars

3.4 CIRCUIT BREAKER INSTALLATION

Use diagonal cutters to cut the metal web of the breaker panel “knock-outs” at the desired breaker locations.

Note: Plug-in Breakers (60 A – 100A) require two mounting positions and a breaker adapter kit.

The breakers are installed by snapping the top terminal onto the upper bus bar and rotating the unit down until the second terminal snaps onto the breaker termination post as shown in Figure 3-

3.The breaker alarm terminals are designed to make contact with the alarm terminal board as the breaker is snapped into place.

**** CAUTION ****

During breaker installation, carefully align the alarm terminals with the alarm terminal board to avoid breaker terminal damage.

12

APC

Image 12
Contents Power Distribution Frame Revision Date Description Table of Contents Precautions General Information IntroductionInspection Upon Receipt of Goods GeneralConcealed Damage Return of Damaged GoodsSystem Configurations Input -48 VDC Bus Circuit BreakersIndicators and Alarms 60A 70A 80A 100AMechanical Specifications EnvironmentalInstallation Procedures Preparation Recommended ToolsRecommended Test Equipment Equipment InspectionMounting diagram MountingCircuit Breaker Installation With splice plates Without splice platesLoad Connections Load connectionsCustomer Service and Support Warranty Provisions General ProvisionsWarranty Returns Warranty Repair or Replacement Exclusions and Limitations