American Power Conversion AP9341 manual Connecting TH Modules

Page 14

Installation—Accessories

Connecting TH Modules

To connect the Main Module to the TH Module:

1.Connect the first TH Module to either port marked A-Link on the rear of the Main Module, using a standard CAT5 (or equivalent) Ethernet patch cable (APC part number 3827BK-10 or equivalent). Do not use a crossover cable for connection.

A-Link is an APC proprietary CAN (Controller Area Network) bus. Devices compatible with A-Link are

Note not Ethernet devices and cannot coexist on an Ethernet bus with other networking devices, such as hubs and switches.

2.Connect the cable from the Main Module to the top A-Link connector labeled (indicating “input”) on the TH Module. Connect the bottom A-Link connector labeled (indicating “output”), to the next TH Module.

3.Plug an APC terminator (0W04161) into the unused A-Link port at each end of the string.

The Main Module does not have to be at the beginning of the chain of cascaded modules. You can cascade TH Modules from both A-Link ports of the Main Module. Always connect the Environmental Manager to the input connector on the TH Module, as described in step 2.

The maximum combined length of all

A-Link cables is 3280 ft (1000 m).

Note

It is not possible to cascade Main

Modules. Install only one Main

Module per system.

Note

10

Temperature/Humidity Module

Image 14
Contents Installation and Quick Configuration Page Contents Page Inventory Preliminary InformationOverview Additional optionsPlease recycle Rear panel Front and Rear Panel ComponentsFront panel Rack-mount installation Installation-TH ModuleToolless peg-mount installation Installation-TH Module Installation-Accessories SensorsInstallation-Accessories To install sensors in another location Alarm beacon User inputs optionalConnecting TH Modules Setting unique identifier numbers Additional TH Modules Accessing a TH Module Upgrading a TH ModuleSpecifications TH ModuleLink Warranty limitations WarrantyLimited warranty Obtaining serviceWarranty Examples of life-support devices Life-Support PolicyGeneral policy Radio Frequency Interference USA-FCCAPC Worldwide Customer Support 990-2380A-00108/2005