Additional TH Modules

Add TH Modules to the Main Module to monitor additional racks. The Main Module can support a maximum of 32 TH Modules (with additional power supplies).

Adding power supplies:

The first time a TH Module receives power, it requests a unique

identification address from the Main Warning Module. It uses this address to

communicate with the Main Module. If the TH Module is not part of the system when it receives power for the first time, it cannot ensure that its identifier is unique, and communication problems may arise.

To avoid communication problems, connect the TH Module to the Main Module or a TH Module that is part of the system before connecting a stabilized power supply to the 24 VDC Input.

Main Module (AP9340)

+G N C N

+

24 12 N O O C

D M

24 VDC

Input

TH Module (AP9341)

24 VDC

Input

TH Module (AP9341)

User Inputs

 

 

 

 

1

2

3

4

+–

+–

+–

+–

User Inputs

 

 

 

 

1

2

3

4

+–

+–

+–

+–

Voltage

Alarm Beacon

Output

 

G D D

 

N 0 1

 

D

 

Voltage

Alarm Beacon

Output

 

G D D

 

N 0 1

 

D

 

aem0078a

Connect the TH Module to the system.

Add a stabilized power supply (AP9505i)

where needed.

If the system includes beacons or devices attached to the +12 VDC or +24 VDC voltage output connector, attach a stabilized power supply (AP9505i) to the 24 VDC Input of every third TH Module.

If the system does not include any beacons or voltage output connections, connect a stabilized power supply (AP9505i) to the 24 VDC Input of every tenth TH Module.

12

Temperature/Humidity Module

Image 16
Contents Installation and Quick Configuration Page Contents Page Preliminary Information OverviewInventory Additional optionsPlease recycle Front panel Front and Rear Panel ComponentsRear panel Toolless peg-mount installation Installation-TH ModuleRack-mount installation Installation-TH Module Installation-Accessories SensorsInstallation-Accessories To install sensors in another location Alarm beacon User inputs optionalConnecting TH Modules Setting unique identifier numbers Additional TH Modules Accessing a TH Module Upgrading a TH ModuleSpecifications TH ModuleLink Warranty Limited warrantyWarranty limitations Obtaining serviceWarranty General policy Life-Support PolicyExamples of life-support devices Radio Frequency Interference USA-FCCAPC Worldwide Customer Support 990-2380A-00108/2005