Specifications

Sensors

Temperature (AP9335T)

Temperature accuracy

±3ºF (±2ºC), from 32 to

 

104ºF (0 to 40ºC)

Sensor operating

14 to 159ºF (–10 to 70ºC)

temperature

 

Maximum length of

50 ft (15.2 m)

cable

 

 

 

A-Link

 

 

 

Maximum length of

3280 ft (1000 m)

cable

 

 

 

Beacon

 

 

 

Maximum length of

330 ft (100 m)

cable

 

 

Temperature/Humidity (AP9335TH), optional

 

 

Temperature accuracy

±3ºF (±2ºC), from 32 to

 

104ºF (0 to 40ºC)

Humidity accuracy

±4% RH, 20 to 90% RH, at

 

77ºF (25ºC)

 

±8% RH, 30 to 80% RH,

 

from 59 to 95ºF (15 to 30ºC)

Sensor operating

14 to 159ºF (–10 to 70ºC)

temperature

 

User input

200 mS

response time

 

Maximum length of

50 ft (15.2 m)

cable

 

 

 

Temperature/Humidity Module

15

Image 19
Contents Installation and Quick Configuration Page Contents Page Additional options Preliminary InformationOverview InventoryPlease recycle Front panel Front and Rear Panel ComponentsRear panel Toolless peg-mount installation Installation-TH ModuleRack-mount installation Installation-TH Module Sensors Installation-AccessoriesInstallation-Accessories To install sensors in another location User inputs optional Alarm beaconConnecting TH Modules Setting unique identifier numbers Additional TH Modules Upgrading a TH Module Accessing a TH ModuleTH Module SpecificationsLink Obtaining service WarrantyLimited warranty Warranty limitationsWarranty General policy Life-Support PolicyExamples of life-support devices USA-FCC Radio Frequency Interference990-2380A-00108/2005 APC Worldwide Customer Support