Operation
Rear of AP7610
| |
| |
|
Serial port: Access internal menus by connecting this port
Status LED: Indicates the status of the network connection and the state of the Rack PDU.
Ethernet port: Connects the Rack PDU to the InfraStruXure™ network, using a
Link LED: Indicates whether there is activity on the network.
Alarm conditions | Configure warning and alarm limits through the internal menus, using a | |||
| serial port connection. |
|
| |
| The Rack PDU shows warning and alarm conditions as follows: | |||
|
|
|
|
|
| Phase Indicator LED |
| Displays yellow for a warning and red for an |
|
|
|
| alarm. |
|
|
|
|
|
|
| Digital display |
| If one phase is at or above the warning or |
|
|
|
| alarm limit, the display shows the current for |
|
|
|
| that phase. |
|
|
|
| If more than one phase is at or above the |
|
|
|
| warning or alarm limit, the display cycles |
|
|
|
| among those phases, displaying their current. |
|
|
|
|
|
|
| Control Button |
| Pressing this button causes the digital display |
|
|
|
| to display the current for the next phase for 30 |
|
|
|
| seconds. Then it returns to the display of the |
|
|
|
| current for any phases that are at or above the |
|
|
|
| warning or alarm limits. |
|
|
|
|
|
|
Do not exceed the maximum voltage and current ratings listed on the rear panel of the Rack PDU.
Warning
Rack Power Distribution Unit — AP7610 | 7 |