APC AP9613, AP9810 Dip switches input and outputs, Configuration Configuration 3 Configuration

Page 12

Dip switches: input and outputs

The table below lists the four possible configurations, with their corresponding inputs and outputs.

Configuration 1

Configuration 2

Configuration 3 Configuration 4*

OFF-OFF-OFF-ON ON-OFF-OFF-ON

OFF-ON-OFF-ON

ON-ON-OFF-ON

Inputs

 

Device Actions

 

 

 

 

 

 

1

Turn the UPS on.

 

 

 

 

 

 

 

 

2

Turn the UPS off.

 

Turn the UPS off

 

 

 

 

safely.

See

 

 

 

 

Configuration

3

Start UPS self-test.

 

 

 

 

 

 

Utility

4

Shut down the UPS

Put the UPS in

Shut down the UPS

 

 

when on battery

bypass, if bypass is

when on battery

 

 

except for self-test or

available on the

except for self-test or

 

 

runtime calibration.

UPS.

runtime calibration.

 

 

 

 

 

 

Outputs

 

 

Device State

 

 

 

 

1

The UPS is on-battery (e.g., during a power failure, self-test, or

 

 

runtime calibration).

 

 

 

 

 

 

2

The UPS has a low battery.

 

 

 

 

 

3

The protected load is not receiving power from the UPS or

 

 

communication between the UPS and the Relay I/O Card has been

 

 

lost.

 

 

 

See

 

 

 

 

 

4

Replace the UPS battery.

UPS commanded to

Configuration

 

 

 

 

turn on

Utility

 

 

 

 

(echo of Input 1).

 

 

 

 

 

 

 

5

The UPS is

 

The UPS is in bypass

UPS commanded to

 

 

overloaded.

 

by selection from

turn off gracefully

 

 

 

 

software, front panel,

(echo of Input 2).

 

 

 

 

or rear panel.

 

 

 

 

 

 

 

 

6

Any UPS fault or

 

Any UPS fault, self-

Any UPS fault, self-

 

 

self-test failure.

 

test failure, or

test failure, overload,

 

 

 

or replace battery

 

 

 

 

overload.

 

 

 

 

 

 

 

 

 

 

* With this setup (the factory default), the Configuration Utility is used automatically.

8

 

Dry Contact I/O SmartSlot Card

 

Image 12
Contents Installation and Configuration AP9613This manual is available in English on the enclosed CD Contents Disclaimer Safety Overview Important Safety InformationProduct Overview IntroductionProduct description Hardware and software requirements and tools needed Itemizing the features of the Dry Contact I/O SmartSlot Card Showing the product detailName Description Itemizing the input contact and output relay terminal blocks Configuring the Dip Switches Location of dip switchesDip switches input and outputs Configuration Configuration 3 ConfigurationInstalling Planning your installationOperating considerations Dry Contact I/O SmartSlot Card Connection strategies Installation steps Dry Contact I/O SmartSlot Card Connecting to the configuration utility Dry Contact I/O SmartSlot Card Specifications ElectricalRatings for input contacts and output relays Voltage Rating Current Rating MaxWarranty Two-Year Factory WarrantyTerms of warranty Non-transferable warranty ExclusionsWarranty claims Disclaimer Page Page Page Page Page Page Page APC Worldwide Customer Support 990-0125D 2013