Installing

See “Planning your installation” directly below, “Installation steps” on page 12, and “Connecting to the configuration utility” on page 14.

Planning your installation

Operating considerations

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Read and understand this manual and the manuals of the UPS before installing this card.

Installation must be performed by qualified personnel.

The user is responsible for compliance with all international and national electric code requirements.

Failure to follow these instructions will result in death or serious injury.

Note the following characteristics of the Dry Contact I/O SmartSlot Card when making decisions regarding system integration:

The coils for all output relays are normally energized. The Card will generate all possible alarms in case of a system fault, such as cable failure, removal of the Dry Contact I/O SmartSlot Card, severe UPS battery discharge, or catastrophic hardware failure on the Card.

All output relays are isolated from each other and from the UPS system ground.

All input contacts are isolated from the UPS system ground but are common to each other

Control inputs are driven by user-supplied dry contact outputs. The dry contact closure sensing voltage available on these inputs is nominally 5 VDC at less than 1 mA. All control inputs are referenced to the UPS system ground.

All control inputs must be stable for a minimum of one second to be considered valid. Longer delays can be set through the Configuration Utility. Control inputs can be asserted indefinitely.

Be careful to assert just a single input to a device. Avoid initiating simultaneous, conflicting actions, e.g. input #1 (turn the UPS on) and input #2 (turn the UPS off).

Control inputs are acted upon immediately after validation. However, there are several UPS conditions that can cause an input to be ineffective, such as self-test or runtime calibration. For confirmation of

Dry Contact I/O SmartSlot Card

9

Image 13
Contents AP9613 Installation and ConfigurationThis manual is available in English on the enclosed CD Contents Disclaimer Important Safety Information Safety OverviewIntroduction Product OverviewProduct description Hardware and software requirements and tools needed Showing the product detail Itemizing the features of the Dry Contact I/O SmartSlot CardName Description Itemizing the input contact and output relay terminal blocks Location of dip switches Configuring the Dip SwitchesConfiguration Configuration 3 Configuration Dip switches input and outputsPlanning your installation InstallingOperating considerations Dry Contact I/O SmartSlot Card Connection strategies Installation steps Dry Contact I/O SmartSlot Card Connecting to the configuration utility Dry Contact I/O SmartSlot Card Electrical SpecificationsVoltage Rating Current Rating Max Ratings for input contacts and output relaysTwo-Year Factory Warranty WarrantyTerms of warranty Non-transferable warranty ExclusionsWarranty claims Disclaimer Page Page Page Page Page Page Page 990-0125D 2013 APC Worldwide Customer Support