APC RS 500 Troubleshooting, Transfer Voltage Adjustment optional, Specifications, Service

Page 2

Troubleshooting

Use the tables below to solve minor Back-UPS RS installation and operation problems. Consult APC On-line Technical Support or call APC Technical Support for assistance with problems that cannot be resolved using this document:

Possible Cause

Procedure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-UPS will not switch on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-UPS RS not connected to an

Check that the Back-UPS RS power plug is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC power source.

securely connected to the wall outlet.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-UPS RS circuit breaker

Disconnect non-essential equipment from the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“tripped”.

Back-UPS RS. Reset the circuit breaker

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(located on the rear panel of the Back-UPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS) by pushing the circuit breaker button

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fully inward until it catches. If the circuit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

breaker resets, switch the Back-UPS RS on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and reconnect the equipment one-at-a-time. If

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the circuit breaker trips again, it is likely that

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

one of the connected devices is causing the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

overload.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Very low or no utility voltage.

Check the wall outlet that supplies power to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the Back-UPS RS using a table lamp. If the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lamp bulb is very dim, have the utility voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

checked by a qualified electrician.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-UPS does not power computer/monitor/external drive during an outage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Internal battery is not connected.

Check the battery connections. (See “Connect the Battery” under

 

“Installation” on the front page of this document.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Computer, monitor or external disk/

Move computer, monitor, or external drive power cord plug to the

CD-ROM drive is plugged into a

Battery Backup outlets.

Surge Only outlet.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-UPS operates on battery although normal utility voltage exists

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-UPS RS circuit breaker

Disconnect non-essential equipment from the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“tripped”.

Back-UPS RS. Reset the circuit breaker

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(located on the rear panel of the Back-UPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS) by pushing the circuit breaker button

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fully inward until it catches.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The wall outlet that the Back-UPS

Connect the Back-UPS RS to another wall outlet or have a qualified

RS is connected to does not supply

electrician check the building wiring.

utility power to the unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-UPS does not provide expected backup time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-UPS RS is excessively

Unplug non-essential Battery Backup connected equipment, such as

loaded.

printers and plug them into Surge Only outlets.

 

Note: Devices that have motors or dimmer switches (laser printers,

 

heaters, fans, lamps, and vacuum cleaners, for example) should not be

 

connected to the Battery Backup outlets.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-UPS RS battery is weak due

Charge the battery. The battery charges whenever the Back-UPS RS

to recent outage and has not had

is connected to a wall outlet. Typically, eight hours of charging time

time to recharge.

are needed to fully charge the battery from total discharge. Back-UPS

 

RS run-time is reduced until the battery is fully charged.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery requires replacement.

Replace battery (see Order Replacement Battery). Batteries typically

 

last 3-6 years, shorter if subjected to frequent power outages or

 

elevated temperatures.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A red indicator is lit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The Overload indicator is lit if

Move one or more equipment power plugs to the Surge Only outlets.

equipment connected to the Battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Backup outlets is drawing more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

power than the Back-UPS RS can

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

provide.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery requires replacement.

The battery should be replaced within two weeks (see "Order

 

Replacement Battery"). Failure to replace the battery will result in

 

reduced run-time during a power outage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-UPS RS failure.

Call APC for service.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace Battery indicator flashing and an alarm sounds when the Back-UPS is turned on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Internal battery not connected.

Check the battery connections.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A red indicator is flashing with any other indicator flashing

Back-UPS RS failure.

Contact APC Online Technical Support.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transfer Voltage Adjustment (optional)

In situations where the Back-UPS RS or connected equipment appears too sensitive to input voltage, it may be necessary to adjust the transfer voltage. This is a simple task requiring use of the front panel pushbutton. To adjust the transfer voltage, proceed as follows:

1.Plug the Back-UPS RS into a utility power source. The Back-UPS RS will be in a Standby Mode (no indicators lit).

2.Press the front panel pushbutton fully inward for 10 seconds. All indicators on the Back-UPS RS will flash to acknowledge going into Programming Mode.

3.The Back-UPS RS will then indicate its current Lower Transfer Voltage, as shown in the following table.

Indicators Lit

Low Transfer Voltage

Use When

1

166 VAC (default)

Normal power conditions exist.

 

 

 

2

160 VAC

Back-UPS RS frequently goes On Battery due to low input voltage.

 

 

 

3

154 VAC

Use only for extreme conditions of low input voltage.

 

 

Not recommended for computer loads.

1.To select 166 volts as the Lower Transfer Voltage, press the pushbutton until 1 indicator is flashing.

2.To select 160 volts as the Lower Transfer Voltage, press the pushbutton until 2 indicators are flashing.

3.To select 154 volts as the Lower Transfer Voltage, press the pushbutton until 3 indicators are flashing. Once in Programming Mode, if the pushbutton is not pressed within 5 seconds, the Back-UPS RS will exit the Programming Mode and all indicators will extinguish.

When selecting 154 volts and the Lower Transfer Voltage, the output current is limited to 2.2 amps to prevent the product from overheating.

Specifications

Output Voltage Regulation

166 - 278 Vac (default setting)

Frequency Limits (on line)

47 - 63 Hz (autosensing)

 

 

On Battery Waveshape

Stepped Sine Wave

 

 

Maximum Load

500 VA - 300 W

 

 

Typical Recharge Time

8 Hours

 

 

Operating Temperature

0o to 40oC (32o to 104oF)

Storage Temperature

-5oto 45oC (23o to 113oF)

Operating and Storage

0 to 95% non-condensing

Relative Humidity

 

Size (H x W x D)

3.6 x 6.5 x 11.2 in. (9.1 x 16.5 x 28.4 cm)

 

 

Weight

15.87 lb (7.2 kg)

 

 

Shipping Weight

500 VA - 15.3 lb (7.0 kg)

 

 

EMI Classification

EN 50091-2, Class B

 

 

On Battery Run-Time

19 Minutes typical - desktop computer and 15 inch (38.1 cm) monitor.

 

 

Service

Note: If the Back-UPS RS requires service, do not return it to the dealer. The following steps should be taken.

1.Consult the Troubleshooting section to eliminate common problems.

2.Determine if the circuit breaker is tripped. If the circuit breaker is tripped, reset the breaker and determine if the problem still exists.

3.If the problem persists, consult the APC Worldwide Web site (www.apcc.com) or call customer service.

Record the model number of the Back-UPS RS, the serial number, and the date purchased. Be prepared to troubleshoot the problem over the telephone with a technician. If this is not successful, the technician will issue a Return Merchandise Authorization Number (RMA#) and a shipping address.

If the Back-UPS RS is under warranty, repairs are free. If not, there is a repair charge.

4.Pack the Back-UPS RS in its original packaging. If the original packing is not available, ask customer service about obtaining a new set. Pack the UPS properly to avoid damage in transit.

Note: Never use StyrofoamTM beads for packaging. Damage sustained in transit is not covered under warranty (insuring the package for full value is recommended).

5.Write the RMA# on the outside of the package.

6.Return the Back-UPS RS by insured, prepaid carrier to the address provided by customer service.

Warranty

The standard warranty is two (2) years from the date of purchase. APC’s standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to assigned asset tags and set depreciation schedules must declare such a need at first contact with an APC Technical Support representative. APC will ship the replacement unit once the defective unit has been received by the repair department, or cross ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to APC. APC pays ground freight transportation costs to ship the replacement to the customer.

Replace the Internal Battery

To replace the internal battery, proceed as follows:

Note: Replacing the battery is a safe procedure. However, small sparks may occur during the process. This is normal.

APC Contact Information

USA/Canada

1.800.800.4272

Worldwide

1.401.789.5735

1

Place the unit on its side. Slide the battery compartment cover up and off of the Back-UPS RS.

2

Pull the battery out of the Back-UPS RS. Disconnect the wires from the terminals.

3

Slide the new battery into the battery compartment. Connect the battery wires to the terminals as follows:

Black wire to Ground (-) terminal Red wire to Positive (+) terminal

4

Align the battery compartment cover with the grooves in the Back-UPS RS. Slide the cover down until it locks.

Home Page

http://www.apc.com

Technical Support http://www.apc.com/support

ESupport esupport@apcc.com

Back-UPS is a registered trademark of American Power Conversion. Copyright © 2000 American Power Conversion. All rights reserved.

For further information contact UPS Direct Ltd:

Tel: 08456 445 002 - Fax: 08456 445 003 - Email: info@upsdirect.com - Website: www.upsdirect.com

Image 2
Contents Connect Phone Lines to Surge Protection Placement / PowerConnect Equipment to the Back-UPS RS Specifications TroubleshootingTransfer Voltage Adjustment optional Service
Related manuals
Manual 2 pages 93 b