Page 24

External Connection

To add card slots, you can daisy-chain the APC Silcon Triple Chassis with the standard Triple Chassis (AP9604) management peripheral, installing the APC Silcon Triple Chassis closer to the UPS.

4.7.4 Powering the APC Silcon Triple Chassis

The APC Silcon Triple Chassis supplies power to the installed management peripheral cards and to the Monitoring port, allowing you to power multiple management peripherals.

4.7.4.1 AP9604S Power Considerations

The AP9604S model of the APC Silcon Triple Chassis receives its power from the UPS through the power connector of the Silcon UPS cable. If the total current required by all the installed management peripherals exceeds 500 mA, you must use a 24 VDC power adapter. To find out whether you need additional power, see “Determining power requirements”.

4.7.4.2 Power Adapters

APC offers two models of 24 VDC power adapter.

The standard adapter (AP9505) can provide an additional 400 mA.

The universal adapter (AP9505i) can provide 850 mA.

4.7.4.3Using a Power Adapter

To use the adapter, plug it into a protected power outlet and into the Optional Power port of the APC Silcon Triple Chassis.

NOTICE!

If the power adapter loses power because of a UPS shutdown, its attached management peripherals may not operate properly, thus adversely affecting the UPS and its protected equipment.

4.7.4.4 AP9604SR Power Considerations

The AP9604SR model receives its power from the UPS through the supplied 24 VDC universal adapter. The total current required by your management peripherals must not exceed the 850 mA limit of the power adapter. See ““Determining power requirements”.

4.7.4.5 Determining Power Requirements:

To determine the total amount of current required by your management peripherals, add the individual current requirements for each management peripheral to be installed with the APC Silcon Triple Chassis to the current requirements of the chassis itself. Refer to this table

Part #

Management Peripheral

Draw (mA)

 

 

 

AP9207

Share-UPS 8-port Interface Expander

65

 

 

 

AP9600

Expansion Chassis

30

 

 

 

AP9604

Triple Chassis

20

 

 

 

990-4053

24

Installation Guide APC Silcon 480kW 400V UPS

Image 24
Contents APC Silcon 480kW 400V UPS Installation Guide Installation Guide APC Silcon 480kW 400V UPS Safety Symbols used in this manualThank You Contents System Specifications Warranty10.0 How to Contact APC AppendixIntroduction IntroductionTools and Equipment ToolsUnpacking UnpackingInstallation InstallationRequirements on Site Height mm Width mm Depth mmFootprint 1 1900mm Cabinet for 480kW UPS2 1600mm Cabinet for 480kW Isolation Transformer FrontConnecting the UPS External ConnectionExternal Connection Right side viewOutput Fuses480kW 1000 185System Integration Interface Connections Parallel Board Terminal Blocks X003/X004 Anxiliary ContactsX005 Output Relays Parallel BoardExternal Connection Power Cables External Control CablesRelay Board RelaysRelay Message Alarm-trigging Events Number Relay Board/Relay FunctionsSee .2 System configuration Communication Interface Board Connecting of APC Silcon Tripel Chassis Safety Warnings APC Silcon Triple ChassisProduct Description Monitoring PortOptional Power Input Installing Management PeripheralsLEDs If the LED is… Then the Silcon Triple Chassis…Installing Management Peripheral Cards Order of Management Peripheral CardsManagement Priority Position Peripheral Card Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA Troubleshooting Problem Possible Cause SolutionIf Problems Persist Product Specifications Monitoring Port Pin Assignments External Connection Power, Physical, and Environmental Specifications PhysicalEnvironmental APC Silcon Battery Cabinets Important Safety InstructionsInstallation of Batteries Diagram UPS with Battery CabinetSilcon Battery Breaker Box/Fuse-box Battery Breaker Box Ampere Connection Max Dimensions Weight Rating Cable ShortCircuit Current kA APC Battery Breaker Box Connection Diagram External Connection Parameter Setting Comments Programming ParametersProgramming Parameters ParametersProgramming Keys System Configuration Programming Example Switch to Bypass OperationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Change parameters by pressing Description of Settings Programming Parameters for Advanced Parallel OperationBattery Monitor Programming exampleOptions/Accessories Options/AccessoriesService Bypass Panel for Single Operation 480 1000 3x185 3x150 800 M12 1825x 250Options/Accessories Operating The External Service Bypass Switch Display showsSwitching from External Bypass to Normal UPS Operation Lamp indication On Servive Bypass PanelService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories H002a Action Options/Accessories Lamp indication On Service Bypass Panel ActionDisplay shows Isolating One UPS for Service/Maintenance Following can be carried out on any UPSSwitching Back to Normal Parallel/Redundant Operation Intersystem Synchronization Unit Intersystem Synchronization Unit System ISU SystemIntersystem Synchronization Unit ISU Remote Display Extension of Remote Display Communication DistanceStandard Short-haul RS232 Modem Async Connections Without Converter Host DTE Remote Display DTEConnections With Converter Pin Connections for cable from host to ME800A-R2 HostRemote Display Power Supply Remote Display CablesCommunication Fault Remote Display SettingAlarms Remote Display UseHeight mm Width mm Depth mm Weight kg 480kW 1800 1600 1950 Isolation TransformerConnecting Isolation Transformer Cable mm2 Signal Isolation External External PEInput Input Cable Output Temp Fuses* FM 185 DIN gL typesOptions/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories System Specifications System SpecificationsTechnical Data Dimensions / WeightWarranty WarrantyAPC Silcon Series Limited Factory Warranty Installation Planning Data AppendixAppendix Appendix How to Contact APC How to Contact APCAPC Corporate APC DenmarkPage