Appendix
9.0Appendix
9.1Table 1. Installation Planning Data
Q3
Service Bypass Panel
Main Input |
|
|
Breaker * |
| Q1 |
| Field | UPS Module |
|
| |
| Wiring* |
|
Output
Q2Breaker*
Field
Wiring*
Battery Bank**
*Not supplied by APC
**Internal Batteries available for 40kW units and smaller
Installation Planning Data
APC Silcon Series
|
|
|
|
|
|
|
|
| AC Input |
|
| Battery System DC |
| AC Output | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Min. Input | Input |
| Full | INom | IMax |
| Load side | Heat |
Power rating | Source | P (kW) | I (A) | Cable | Overcurrent | Vn | load | Disch | Disch | In | Overcurrent | Dissipation | |||||||
kW |
| kVA |
| Pf | V | Hz | Nom. | Max. | Nom. | Max. | (per phase) | Protection* | (Vdc) | P(kW) | (A) | (A) | (A) | Protection* | (kW) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
480 |
| 480 |
| 1 | 380 | 50/60 | 491.8 | 569.5 | 838.3 | 922.1 | 3//185mm2 | 1000 A | 2x384 | 505.3 | 658 | 775 | 727.3 | 800 A | 15.9 |
|
|
|
|
| 400 |
|
|
| 747.3 | 822.0 |
|
|
|
|
|
| 695.7 |
|
|
|
|
|
|
| 415 |
|
|
| 768.4 | 845.2 |
|
|
|
|
|
| 666.7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| COLUMN |
| 1a | 1b | 1c | 1d | 1e | 1f | 1g | 1h | 2a | 2b | 2c | 2d | 3a | 3b | 4a | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| NOTES |
|
|
| 3 | 4 | 1 | 2 | 9 | 5, 6, 13 | 8 | 12 | 10 | 11 |
| 6, 7 | 13 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
* Provided by others |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Installation Guide APC Silcon 480kW 400V UPS | 71 |