APC 990-4053 Programming Parameters for Advanced Parallel Operation, Description of Settings

Page 41

Programming Parameters

5.3Programming Parameters for Advanced Parallel Operation

To use the advanced parallel functions, the following parameters must be programmed:

1.“Station number”

2.“Highest station address”

3.“Advanced power management”

4.“APM test mode active”

5.“Battery connection”

5.3.1 Description of Settings

1.“Station number”

Valid station numbers: 1-9 stating the UPS parallel address in system.

2.“Highest station number”

Valid station numbers: 2-9 stating the number of UPSs in system.

3.“Advanced power management”

“Disabled”: Advanced Power Management is inactive.

“PARALLEL+1”: Advanced Power Management is activated when the system operates as PARALLEL N+1, meaning that one system can be isolated without overloading the remaining systems (N systems/UPSs).

“REDUNDANT+1”: Advanced power management is activated when the system operates as REDUNDANT N+1, meaning that one system can be isolated without overloading the remaining systems (N systems/UPSs) with one spare system.

4.“APM test mode active”

“No”: Stand-by-time will be 24 hours - on-line time will be 48 hours (xN systems).

“Yes”: Stand-by-time will be 1 min. - on-line time will be 2 min (xN systems).

5.“Battery connection”

“Separate”: Separate battery for this UPS.

“Common”: Common battery in a parallel system.

NOTICE!

“Common”: Common battery in a parallel system. When this setting is chosen, the highest battery temperature that can be found in the parallelled systems (for charge voltage compensation).

NOTICE!

Common battery pack is a technical possibility.

However, APC recommend separate battery pack due to a higher safety degree in connection with redundant/parallel operation.

The UPS system is designed for both situations.

990-4053

Installation Guide APC Silcon 480kW 400V UPS

41

Image 41
Contents APC Silcon 480kW 400V UPS Installation Guide Thank You Installation Guide APC Silcon 480kW 400V UPSSafety Symbols used in this manual Contents Warranty System Specifications10.0 How to Contact APC AppendixIntroduction IntroductionTools and Equipment ToolsUnpacking UnpackingInstallation InstallationRequirements on Site Height mm Width mm Depth mm1 1900mm Cabinet for 480kW UPS Footprint2 1600mm Cabinet for 480kW Isolation Transformer FrontExternal Connection Connecting the UPSExternal Connection Right side viewFuses Output480kW 1000 185System Integration Interface Connections Terminal Blocks X003/X004 Anxiliary Contacts Parallel BoardX005 Output Relays Parallel BoardExternal Connection External Control Cables Power CablesRelays Relay BoardRelay Board/Relay Functions Relay Message Alarm-trigging Events NumberSee .2 System configuration Communication Interface Board Connecting of APC Silcon Tripel Chassis APC Silcon Triple Chassis Safety WarningsProduct Description Monitoring PortInstalling Management Peripherals Optional Power InputLEDs If the LED is… Then the Silcon Triple Chassis…Order of Management Peripheral Cards Installing Management Peripheral CardsManagement Priority Position Peripheral Card Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA If Problems Persist TroubleshootingProblem Possible Cause Solution Product Specifications Monitoring Port Pin Assignments External Connection Environmental Power, Physical, and Environmental SpecificationsPhysical Important Safety Instructions APC Silcon Battery CabinetsSilcon Installation of BatteriesDiagram UPS with Battery Cabinet Battery Breaker Box/Fuse-box Circuit Current kA Battery Breaker BoxAmpere Connection Max Dimensions Weight Rating Cable Short APC Battery Breaker Box Connection Diagram External Connection Programming Parameters Parameter Setting CommentsProgramming Parameters ParametersProgramming Keys Programming Example Switch to Bypass Operation System ConfigurationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Change parameters by pressing Programming Parameters for Advanced Parallel Operation Description of SettingsProgramming example Battery MonitorOptions/Accessories Options/AccessoriesService Bypass Panel for Single Operation 480 1000 3x185 3x150 800 M12 1825x 250Options/Accessories Display shows Operating The External Service Bypass SwitchLamp indication On Servive Bypass Panel Switching from External Bypass to Normal UPS OperationService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories H002a Action Options/Accessories Display shows Lamp indication On Service Bypass PanelAction Following can be carried out on any UPS Isolating One UPS for Service/MaintenanceSwitching Back to Normal Parallel/Redundant Operation Intersystem Synchronization Unit ISU Intersystem Synchronization UnitIntersystem Synchronization Unit System ISU System Standard Short-haul RS232 Modem Async Remote DisplayExtension of Remote Display Communication Distance Host DTE Remote Display DTE Connections Without ConverterConnections With Converter Pin Connections for cable from host to ME800A-R2 HostRemote Display Cables Remote Display Power SupplyRemote Display Setting Communication FaultAlarms Remote Display UseIsolation Transformer Height mm Width mm Depth mm Weight kg 480kW 1800 1600 1950Connecting Isolation Transformer Isolation External External PE Cable mm2 SignalInput Input Cable Output Temp Fuses* FM 185 DIN gL typesOptions/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories System Specifications System SpecificationsTechnical Data Dimensions / WeightAPC Silcon Series Limited Factory Warranty WarrantyWarranty Appendix Installation Planning DataAppendix Appendix How to Contact APC How to Contact APCAPC Corporate APC DenmarkPage