APC SYPM2KU, 990-1031, SYBT2 installation manual Rear View Component Identification

Page 12

Rear View Component Identification

 

Œ •

Ž

Figure 3: Rear View of the Symmetra RM (200/208 Vac / L1-L2-G version shown)

System Fan Œ: The system fan can be replaced in the field. Refer to Replacing the System Fan, in the SYMMETRA RM OPERATION MANUAL, for instructions.

Accessory Ports : APC manufactures a set of auxiliary user interface accessories. The Symmetra RM contains a total of three accessory ports. The top slot is preloaded with the SYCC card that provides computer and battery ports. Two unoccupied accessory slots is provided. The Symmetra RM also includes a Web/SNMP Management Card for accessing data via a network. Other accessory options are available, including:

Out-of-Band Monitoring Card (formerly named CallUPS) initiates telephone notification of power event

Environmental Monitoring Card (formerly named MeasureUPS) monitors environmental conditions

Control-UPS control and monitor via modem

Use only accessory devices labeled “Symmetra compatible.”

External Battery Cabinet Connector Ž: Connect an External Battery Cabinet to the Symmetra RM using this connector. The Symmetra RM can connect to a maximum of seven external battery cabinets in a daisy- chain fashion.

Power Distribution Panel (PDU) : The type of power panel depends on the voltage range of the Symmetra RM. Figure 3 shows a Symmetra RM with a 200/208 Vac (L1-L2-G) power panel. It contains one L6-30 and two L6-20 receptacles. The 220/230/240 Vac (L1-N-G) power panel contains eight IEC C13 and two IEC C19 receptacles. Figure 8, page 16, shows the two PDU panels. The PDU panel can be changed in the field by a qualified technician or electrician.

Input Circuit Breaker : The input circuit breaker, located at the back of the frame, protects the Symmetra RM from extreme overloads. When switched to Stand By the Symmetra RM is disconnected from incoming utility voltage. When switched to the On position, power flows from the utility source into the Symmetra RM. Under normal operating conditions, the input circuit breaker always remains in the On position.

Emergency Power Off (EPO) Switch Connection : Use this connection to wire the Symmetra RM to an emergency power off switch located away from the unit. This switch shuts off power to Symmetra RM and prevents the unit from operating on-battery. The terminal connections for the EPO switch are physically isolated from the primary circuitry of the Symmetra RM. See Wire the Emergency Power Off (EPO) Switch, page 14, for wiring instructions.

EPO wiring must be installed by a qualified electrician only.

8

Image 12
Contents APC Symmetra RM Installation Manual Limited Warranty Life Support PolicyTable of Contents List of Figures Handling Safety Electrical SafetyConventions Used in this Manual Deenergizing Safety Battery SafetyRecycling of Batteries Radio Frequency InterferencePage About Your UPS Description Option End Item SKUHow To Contact APC North AmericaLatin America, South America Europe, Middle East, and AfricaProduct Overview Front View Component IdentificationUse only accessory devices labeled Symmetra compatible Rear View Component IdentificationPage System Block Diagram MIMInstalling the Symmetra RM UnpackingDetermine the Location of the Symmetra RM in the Rack Connect the Symmetra RM to its Power Source Install the UPS into the RackWire the Emergency Power Off EPO Switch Use only a qualified electrician to install the EPO wiringInstall Modules Into the Symmetra RM Frame CL2XConnect Equipment to the Symmetra RM 220/230/240 L1-N-G PDU Panel 200/208 L1-L2-G PDU PanelAppendix a Electrical Wiring Checklist Vin