APC SYPM2KU, 990-1031, SYBT2 installation manual Unpacking, Installing the Symmetra RM

Page 15

CHAPTER 3: INSTALLATION

Unpacking

APC has taken care to design robust packaging for your product. However, accidents and damage may occur during shipment.

Inspection

Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly.

Contents

The shipping package contains the UPS, one PowerView display bezel, three blank bezels, the mounting rail kit (containing the mounting rails, and hardware), one blank panel kit (containing five blank panels, screws and instructions), and a literature kit.

Placement

The Symmetra RM is designed for use in a data center or other office environment. Install it in a protected area that is free of excessive dust, corrosion, conductive contaminants, and has adequate air flow. Do not operate the UPS where the temperature and humidity are outside the specified limits.

Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the warranty.

Installing the Symmetra RM

Installing the Symmetra RM is a five-step process:

1.Position the Symmetra RM where it will be used. (This step includes mounting it in a rack if desired.)

2.Connect the Symmetra RM to its power source.

3.Wire the Emergency Power Off (EPO) switch.

4.Install modules into the Symmetra RM frame.

5.Connect equipment to the Symmetra RM.

This section describes each step in detail.

Position the Symmetra RM

Do not install the battery module(s) in the frame until you are ready to power up the Symmetra RM. Failure to do so can result in a deep discharge of the batteries, which may cause permanent damage.

Mounting rails are included with the Symmetra RM. The rails support the unit in the rack and provide adequate air flow.

The Symmetra RM requires two people to install due to its weight.

11

Image 15
Contents APC Symmetra RM Installation Manual Life Support Policy Limited WarrantyTable of Contents List of Figures Handling Safety Electrical SafetyConventions Used in this Manual Battery Safety Deenergizing SafetyRadio Frequency Interference Recycling of BatteriesPage Description Option End Item SKU About Your UPSEurope, Middle East, and Africa How To Contact APCNorth America Latin America, South AmericaFront View Component Identification Product OverviewRear View Component Identification Use only accessory devices labeled Symmetra compatiblePage MIM System Block DiagramUnpacking Installing the Symmetra RMDetermine the Location of the Symmetra RM in the Rack Install the UPS into the Rack Connect the Symmetra RM to its Power SourceUse only a qualified electrician to install the EPO wiring Wire the Emergency Power Off EPO SwitchCL2X Install Modules Into the Symmetra RM Frame220/230/240 L1-N-G PDU Panel 200/208 L1-L2-G PDU Panel Connect Equipment to the Symmetra RMAppendix a Electrical Wiring Checklist Vin