Install the UPS into the Rack

1. With two people supporting the Symmetra RM, one on each side, carefully align the cleats on the sides of the unit with the grooves on the mounting rails. Slide the unit into the rack completely.

2. Use the six (6) ornamental screws, supplied with the unit, to attach the mounting brackets to the rack post.

Connect the Symmetra RM to its Power Source

200/208/240 Vac (L1-L2-G) Symmetra RM: The input power can be supplied in two ways: the attached line cord can be plugged into an appropriate outlet; or the power can be hard wired. Use the line cord if the load is

5 kVA. If the load is greater than 5 kVA you must hard wire the input power. 220/230/240 Vac (L1-N-G) Symmetra RM: The input power must be hard wired.

How to Connect the Input Line Cord

If your Symmetra RM is configured for 200/208 Vac (L1-L2-G) and has a load of 5 kVA or less, use the line cord to power the Symmetra RM. No wiring is necessary.

220/230/240

1.

Set the input select switch to 200/208 (L1-L2-G).

200/208

2.

Plug the standard 208 Vac L6-30 power cord into a 30 Amp

 

208 Vac outlet.

How to Hard Wire the Symmetra RM

Verify that all incoming line voltage (utility power) and low voltage (control) circuits are de-energized, and locked out before installing cables or making connections, whether in the junction box or to the Symmetra RM.

Verify that the battery modules have not been installed in the Symmetra RM. If battery module(s) have been installed, remove them before installing any wiring.

Only an authorized electrician should install all power and control wiring, according to national and local regulations.

Hard wire the input power on all 220/230/240 Vac (L1-N-G) units and on any 200/208 (L1-L2-G) unit with a load greater than 5 kVA.

Use flexible metal conduit to make maintenance and service easier.

13

Image 17
Contents APC Symmetra RM Installation Manual Life Support Policy Limited WarrantyTable of Contents List of Figures Conventions Used in this Manual Handling SafetyElectrical Safety Battery Safety Deenergizing SafetyRadio Frequency Interference Recycling of BatteriesPage Description Option End Item SKU About Your UPSNorth America How To Contact APCLatin America, South America Europe, Middle East, and AfricaFront View Component Identification Product OverviewRear View Component Identification Use only accessory devices labeled Symmetra compatiblePage MIM System Block DiagramUnpacking Installing the Symmetra RMDetermine the Location of the Symmetra RM in the Rack Install the UPS into the Rack Connect the Symmetra RM to its Power SourceUse only a qualified electrician to install the EPO wiring Wire the Emergency Power Off EPO SwitchCL2X Install Modules Into the Symmetra RM Frame220/230/240 L1-N-G PDU Panel 200/208 L1-L2-G PDU Panel Connect Equipment to the Symmetra RMAppendix a Electrical Wiring Checklist Vin