APC specifications APC Symmetra LX, Part 1 General Summary

Page 1

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM

APC Symmetra LX

GUIDE SPECIFICATIONS FOR

4kVA-16kVA

Uninterruptible Power System

PART 1 - GENERAL

1.1SUMMARY

A.This specification describes the operation and functionality of a continuous duty, single- phase, solid-state, static Uninterruptible Power System (UPS) hereafter referred to as the UPS.

B.The UPS shall utilize modular power protection technology designed to allow internal redundancy, scalability of power and runtime, and fast mean time to repair (MTTR). The UPS should be configured from five basic components- UPS frames, extended run battery frames (XR frames), power modules, battery modules, and intelligence modules. UPS and XR frames should be capable of shipping with modules installed. XR frames should be capable of communicating battery and runtime status to intelligence modules. Power, battery, and intelligence modules should be hot-swappable and user-replaceable for fast MTTR.

C.Configuration Specifics:

1.The UPS frame(s) should be capable of the following configurations:

____4-8kVA N+1 Redundant Tower

____4-16kVA N+1 Redundant Tower

____4-16kVA N+1 Redundant Tower with nine (9) extra Battery Module slots

____4-8kVA N+1 Redundant 13U Rack-mount

____4-16kVA N+1 Redundant 19U Rack-mount

2.The system power train shall be comprised of hot-swappable, user-replaceable 3.2kW/4kVA and 10% Battery charger circuit power modules, which shall operate in parallel, and be configurable for N+1 redundant operation at rated load.

3.The system shall also include a field-replaceable internal automatic and manual bypass system module, field-replaceable output power distribution panels, removable input/output wiring tray, standard redundant intelligent modules, battery disconnects, an LCD interface display, EPO, and an integrated UPS network management card with temperature monitoring.

D.In addition, this specification describes the performance, functionality, and design of the UPS Service Bypass Panel, hereafter referred to as the SBP, the external Battery Systems, and connectivity solutions.

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM

Image 1
Contents Part 1 General Summary APC Symmetra LXCSA StandardsModes of Operation Part 2 Product Design Requirements SubmittalsSystem Characteristics Environmental Input Power ConverterOutput Inverter Display and Controls Automatic BypassCSI Static Uninterruptible System CSI Static Uninterruptible System Battery Removable INPUT/OUPUT Electrical Terminal Part 3 Accessories Service Bypass Panel SBPSoftware and Connectivity Software Compatibility Remote UPS MonitoringFactory Assisted START-UP CSI Static Uninterruptible System Maintenance Contracts Manufacturer Field ServiceTraining