CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
F.External Service Bypass Panel (SBP): The maintenance service bypass cabinet shall provide power to the critical load bus from the bypass source, during times where maintenance or service of the UPS frame is required or when removal of the frame is desired. The SBP shall provide a mechanical means of complete isolation of the UPS from the electrical wiring of the installation. The SBP shall be constructed in a free- standing, rack mounted or
1.4SUBMITTALS
A.Proposal Submittals:
1.As bid system bill of materials.
2.Product catalog sheets or equipment brochures.
3.Product guide specifications.
4.System
5.Installation information, including weights and dimensions.
6.Information about terminal locations for power and control connections.
B.Delivery Submittals:
1.Installation manual, which includes instructions for storage, handling, examination, preparation, installation, and
2.User manual, which includes operating instructions.
PART 2 – PRODUCT
2.1DESIGN REQUIREMENTS
A.The UPS shall be sized for initial capacity of _____ kVA and _____ kW load.
B.The UPS shall be scalable to final capacity of _____ kVA and _____ kW load.
C.The UPS battery shall be sized for _____ kVA at a Power Factor of_____ for _____
minutes.
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM