APC LX specifications Submittals, Part 2 Product Design Requirements

Page 3

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM

F.External Service Bypass Panel (SBP): The maintenance service bypass cabinet shall provide power to the critical load bus from the bypass source, during times where maintenance or service of the UPS frame is required or when removal of the frame is desired. The SBP shall provide a mechanical means of complete isolation of the UPS from the electrical wiring of the installation. The SBP shall be constructed in a free- standing, rack mounted or wall-mounted NEMA 1 enclosure unless otherwise stated in this specification. It shall be designed for either three phase input or single phase input with a “ no break” transfer between bypass and UPS power.

1.4SUBMITTALS

A.Proposal Submittals:

1.As bid system bill of materials.

2.Product catalog sheets or equipment brochures.

3.Product guide specifications.

4.System single-line operation diagram.

5.Installation information, including weights and dimensions.

6.Information about terminal locations for power and control connections.

B.Delivery Submittals:

1.Installation manual, which includes instructions for storage, handling, examination, preparation, installation, and start-up of UPS.

2.User manual, which includes operating instructions.

PART 2 – PRODUCT

2.1DESIGN REQUIREMENTS

A.The UPS shall be sized for initial capacity of _____ kVA and _____ kW load.

B.The UPS shall be scalable to final capacity of _____ kVA and _____ kW load.

C.The UPS battery shall be sized for _____ kVA at a Power Factor of_____ for _____

minutes.

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM

Image 3
Contents Part 1 General Summary APC Symmetra LXStandards CSAModes of Operation Part 2 Product Design Requirements SubmittalsSystem Characteristics Environmental Input Power ConverterOutput Inverter Display and Controls Automatic BypassCSI Static Uninterruptible System CSI Static Uninterruptible System Battery Part 3 Accessories Service Bypass Panel SBP Removable INPUT/OUPUT Electrical TerminalSoftware and Connectivity Remote UPS Monitoring Software CompatibilityFactory Assisted START-UP CSI Static Uninterruptible System Manufacturer Field Service Maintenance ContractsTraining