CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
2.2SYSTEM CHARACTERISTICS
A.System Capacity: The system shall be rated for .8 Pf output in the following frame sizes:
1.8 kVA/ 6.4kW - Can be configured with up to (3), 3.2kW power modules for N+1
2.16 kVA/ 12.8kW - Can be configured with up to (5), 3.2kW power modules for N+1
B.Input:
1.AC Input Nominal Voltage: 208 V or 240V, Single Phase, 4 wire (2 Phase+ N + G), 60 Hz.
2.AC Input Voltage Window: 155
3.Maximum Frequency Range:
4.Input Power Factor:
a.Minimum .90 lagging at 100% load at 208 V
b.Minimum .98 lagging at 100% at 240 V
6.Input Current Distortion with no additional filters: a. < 5% at 100% load at 240V
D. UPS Output:
1.AC Output Nominal Output: 120/208V or 120/240V , Single Phase, 4 wire (2Phase + N + G), 50 or 60 Hz.
2.AC Output Voltage Distortion: Max. 5% @ 100% Linear Load, phase to neutral loads.
3.AC Output Voltage Regulation: +/- 3% For 100 % Linear or Nonlinear Load, phase to neutral loads.
4.Voltage Transient Response: +/- 5% maximum for 100% load step
5.Voltage Transient Recovery within <60 milliseconds
6.Output Voltage Harmonic Distortion:
a.<2% THD maximum and 1% single harmonic for a 100% linear load
b.<5% THD maximum for a 100%
7.Overload Rating:
a.Normal Operation:
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM