APC LX specifications Standards, Csa, Modes of Operation

Page 2

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM

E.The UPS and associated equipment shall operate in conjunction with a primary power supply and an output distribution system to provide quality uninterrupted power for mission critical, electronic equipment load.

F.All programming and miscellaneous components for a fully operational system as described in this specification shall be available as part of the UPS.

1.2STANDARDS

A.UL 1778 Uninterruptible Power Supply Equipment

B.CSA

C.FCC Class A

D.ISO 9001

E.ISO 14001

1.3MODES OF OPERATION

A.Normal: The input converter and output inverter shall operate in an on-line manner to continuously regulate power to the critical load. The input and output converters shall be capable of full battery recharge while simultaneously providing regulated power to the load for all line and load conditions within the range of the UPS specifications.

B.Battery: Upon failure of the AC input source, the critical load shall continue being supplied by the output inverter, which shall derive its power from the battery system. There shall be no interruption in power to the critical load during both transfers to battery operation and retransfers from battery to normal operation.

C.Recharge: Upon restoration of the AC input source, the input converter and output inverter shall simultaneously recharge the battery and provide regulated power to the critical load.

D.Automatic Bypass: The automatic bypass shall be used to provide transfer of critical load from the Inverter output to the bypass source. This transfer, along with its retransfer, shall take place with no power interruption to the critical load. In the event of an emergency, this transfer shall be an automatic function.

E.Manuel Bypass: The system shall be equipped with an internal make-before-break two pole switch to electrically isolate the UPS from the input and output during preventative maintenance, module upgrades, or limited frame service. The manual bypass shall also be considered a partial ‘wrap-around’ bypass, and shall be configured to wrap around the power modules (recitifier, battery charger, inverter) , and battery modules in the same manner as the automatic bypass will still supplying surge and EMI filtering, and overcurrent protection. There will be a positional sense supplied to alert users that the UPS is in manual bypass.

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM

Image 2
Contents APC Symmetra LX Part 1 General SummaryModes of Operation StandardsCSA Submittals Part 2 Product Design RequirementsSystem Characteristics Input Power Converter EnvironmentalOutput Inverter Automatic Bypass Display and ControlsCSI Static Uninterruptible System CSI Static Uninterruptible System Battery Software and Connectivity Part 3 Accessories Service Bypass Panel SBPRemovable INPUT/OUPUT Electrical Terminal Factory Assisted START-UP Remote UPS MonitoringSoftware Compatibility CSI Static Uninterruptible System Training Manufacturer Field ServiceMaintenance Contracts