CHAPTER 2: BASIC COMMANDS
Language Setting (continued)
6.Locate the language program file to be downloaded into the UPS.
See the APC website at http://www.apc.com/support and download the desired language.
7.Place the PowerView in programming mode simultaneously pressing the three keys on the right (‘Esc’, ‘Help’, and ‘ENTER’) for approximately three seconds, until the PowerView emits a long beep.
•The LCD will display the Programming screen.
•To leave the Programming screen before starting a file transfer (Step 6), press ‘ESC’ until the beep (about one second).
8.Start HyperTerminal or another terminal emulation program on the computer.
•Set the communication parameters to 8 bits, no parity, no flow control, 1 stop bit, and 19,200 bps.
•After establishing a connection, use the Xmodem protocol to transfer the language program file from PowerView.
•When the file transfer is complete, the PowerView will reset itself and display the
9.If the file transfer fails, PowerView will reset itself. Retry the file transfer by repeating Step 6 and Step 7.
10.Quit the terminal session.
11.Disconnect the programming cable on the PowerView
12.Connect the UPS cable to the PowerView
13.Install the display bracket to the rear of the PowerView by securing the two screws to the display.
14.With two hands, grip the display and gently snap the tabs onto the frame.
15.Secure the PowerView display by tightening the two screws to the UPS frame.
8