CHAPTER 3: MENU COMMANDS
Setup Menu
The Setup Menu allows the user to customize the UPS functionality.
| Menu Item |
| Function | Options |
|
|
|
|
|
| Shutdown |
| Sets the shutdown parameters in the event of a | None |
|
| utility power failure. |
| |
|
|
|
| |
|
|
|
|
|
| Low Batt(ery) |
| Sets the number of minutes an audible alarm | 2 (default), 5, 7, 10, 12, 15, |
| Dur(ation) |
| sounds before the UPS shuts down due to battery | 18, or 20 minutes |
|
|
| exhaustion. |
|
|
|
|
| |
| Shutdown Delay | Sets the additional runtime for computer issuing | 0, 20 (default), 60, 120, 240, | |
|
|
| shutdown command if it needs additional time to | 480, 720, or 960 seconds |
|
|
| shut itself down. |
|
|
|
|
| |
| Return Delay | Sets the delay interval that allows utility power to | 0 (default), 20, 60, 120, 240, | |
|
|
| stabilize before the system goes back online after a | 480, 720, or 960 seconds |
|
|
| utility power failure. |
|
|
|
|
|
|
| Return Battery |
| Sets the minimum battery capacity necessary | 0 (default), 15, 25, 35, 50, |
| Capacity |
| before repowering the load when returning from an | 60, 75, or 90 seconds |
|
|
| extended utility power failure. |
|
|
|
|
|
|
| Defaults |
| Sets all settings to factory defaults. |
|
|
|
|
|
|
| Output Freq(uency) |
| The UPS output will phase lock to the input within | 50 ±3 Hz, 50 ± 0.1 Hz, 60 ± |
|
|
| this range. | 3 Hz, 60 ± 0.1 Hz, Full range |
|
|
|
| tracking |
|
|
|
|
|
13