APC SYBATT manual Setup Menu, Menu Item Function Options

Page 17

CHAPTER 3: MENU COMMANDS

Setup Menu

The Setup Menu allows the user to customize the UPS functionality.

 

Menu Item

 

Function

Options

 

 

 

 

 

 

Shutdown

 

Sets the shutdown parameters in the event of a

None

 

 

utility power failure.

 

 

 

 

 

 

 

 

 

 

 

Low Batt(ery)

 

Sets the number of minutes an audible alarm

2 (default), 5, 7, 10, 12, 15,

 

Dur(ation)

 

sounds before the UPS shuts down due to battery

18, or 20 minutes

 

 

 

exhaustion.

 

 

 

 

 

 

Shutdown Delay

Sets the additional runtime for computer issuing

0, 20 (default), 60, 120, 240,

 

 

 

shutdown command if it needs additional time to

480, 720, or 960 seconds

 

 

 

shut itself down.

 

 

 

 

 

 

Return Delay

Sets the delay interval that allows utility power to

0 (default), 20, 60, 120, 240,

 

 

 

stabilize before the system goes back online after a

480, 720, or 960 seconds

 

 

 

utility power failure.

 

 

 

 

 

 

 

Return Battery

 

Sets the minimum battery capacity necessary

0 (default), 15, 25, 35, 50,

 

Capacity

 

before repowering the load when returning from an

60, 75, or 90 seconds

 

 

 

extended utility power failure.

 

 

 

 

 

 

 

Defaults

 

Sets all settings to factory defaults.

 

 

 

 

 

 

 

Output Freq(uency)

 

The UPS output will phase lock to the input within

50 ±3 Hz, 50 ± 0.1 Hz, 60 ±

 

 

 

this range.

3 Hz, 60 ± 0.1 Hz, Full range

 

 

 

 

tracking

 

 

 

 

 

13

Image 17
Contents Symmetra LX Operations Guide Page Table of Contents Page Keys and Indicators PowerViewStatus Indicator Color OverviewMenu Description NavigationSupply Power to the UPS Basic CommandsSet the Correct Output Voltage Supply Power to the Load EquipmentBypass Operation Turn Off UPS Output Power and Load EquipmentCommand Bypass Language Setting Language Setting Control Menu Menu CommandsAccessories Menu Display Function Options Display MenuHelp Menu Diagnostics MenuLogging Menu Menu Item FunctionStatus Menu Menu Item Function Options Setup MenuUS/JAPAN Condition PowerView Message Reason Corrective Action TroubleshootingTroubleshooting Symmetra LX Physical Troubleshooting Troubleshooting Troubleshooting Service