CHAPTER 4: TROUBLESHOOTING
Condition | PowerView Message | Reason | Corrective Action |
|
|
|
|
General Fault | Input circuit breaker | The input circuit breaker on the | Option 1: If this occurs in |
(continued) | tripped open. | UPS tripped open. Input voltage is | conjunction with an overload |
|
| disconnected from the UPS. | condition, decrease the load |
|
|
| and reset the breaker. |
|
|
| Option 2: If no overload |
|
|
| condition exists, reset the |
|
|
| breaker. If the breaker trips |
|
|
| open again, call contract |
|
|
| service provider or APC |
|
|
| Technical Support. |
|
|
|
|
| System level fan failed. | A cooling fan in the UPS frame | Call contract service provider |
|
| failed. | or APC Technical Support. |
|
|
|
|
| The Redundant | The intelligence module in the | Replace the intelligence |
| Intelligence Module (IM) | lower IM slot has failed or is not | module. Refer to module |
| is in control. | installed. The intelligence module | replacement procedure. |
|
| in the upper IM slot is managing all |
|
|
| activity. |
|
|
|
|
|
| IIC | The communications between the | Call contract service provider |
| communications failed. | MIM and at least one other module | or APC Technical Support. |
|
| failed. |
|
|
|
|
|
20