American Power Conversion 5000I user manual Initial Startup

Page 12

Initial Startup

Rear Views

5000 VA Tower Model

5000 VA Rack Mount Model

Charge the battery

The UPS charges its battery whenever it is connected to utility power. The battery will charge fully during the first four hours of normal operation. Do not expect full runtime during this initial charge period.

Connect Computer Interface Port (Optional)

Power management software and interface kits can be used with this UPS. Use only kits supplied or approved by the manufacturer. If used, connect the interface cable to the 9-pin computer interface port on the back panel of the UPS. Secure the connector’s screws to complete the connection.

Caution:

DO NOT use a standard serial interface cable to connect to the Computer Interface Port on the UPS. Standard

serial interface cables are incompatible with the UPS connector. Use the cable provided with your UPS.

Connect Ground Leads to TVSS Connector (Optional)

The UPS features a TVSS connector for connecting the ground lead on transient voltage surge-suppression (TVSS) devices such as telephone and network line protectors. The TVSS connector provides grounding through the UPS’s power cord ground conductor. To make a connection to the TVSS connector, loosen the screw and connect the surge suppression device’s ground lead. Tighten the screw to secure the lead.

Voltage Sensitivity

The UPS detects line voltage distortions such as spikes, notches, dips, and swells, as well as distortions caused by operation with inexpensive fuel-powered generators. By default, the UPS reacts to distortions by transferring to on-battery operation to protect the loads. Where power quality is poor, the UPS may frequently transfer to on-battery operation. If the loads can operate normally under such conditions, battery capacity and service life may be conserved by reducing the sensitivity of the UPS.

To reduce UPS sensitivity, press the configuration button on the rear panel. Use a pointed object such as a pen to press the button. Press it once to set the UPS’s sensitivity to reduced. Press it again to set the sensitivity to low. Press the button a third time to reset normal sensitivity.

normal

reduced

low

When the UPS is set to normal sensitivity, the configuration LED is brightly lit. When it is set to reduced sensitivity, the LED is dimly lit.

When it is set to low sensitivity, the LED is off.

990-7032A, Revision 3 7/01

6

Image 12
Contents 990-7032A, Revision 3 7/01 990-7032A, Revision 3 7/01 Handling Safety Electrical SafetyReplacement and Recycling of Batteries Page Table of Contents Page Contents How to Unpack the UPSIntroduction UnpackingInstallation PlacementInstalling Rack Mount Units Position the UPSInstall the Mounting Rails in the Rack Hardwire the Electrical Connection Load the UPS into the RackInstall the Batteries Connect Power and Equipment to the UPSConnect Power to the UPS Install PowerChute and AccessoriesInitial Startup Low Battery Warning Interval Operating Instructions Storage Replacing the Battery User Configuration Items How to Determine On-Battery Run TimeUPS battery life differs based on usage and environment Tower and 5U Rack Mount 5000 VA ModelsSpecifications Regulatory Agency Approvals Troubleshooting Service Limited WarrantyIf the UPS requires service do not return it to the dealer APC Contact InformationRacks Rack Type Hole Type Hardware Required Hardware IncludedAppendix B Transporting Your Smart-UPS