Replacing the Battery

This UPS has an easy to replace hot-swappable battery. The battery compartment is located on the front panel for easy access. Battery replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and loads on for the following procedure. See your dealer or call the number in this manual for information on replacement battery cartridges.

Note:

Please read the cautions in Smart UPS Safety Guide, at the front of this manual. Once the battery is disconnected,

the loads are not protected from power outages.

Model #

Replacement Battery Cartridge (RBC) #

SU5000I

RBC 12

 

 

SU5000RMI5U

RBC 12

 

 

Note:

Graphics are not drawn to scale. They are shown for reference only.

1.Remove the front bezel by grasping the finger clips on the side of the bezel and carefully

loosening the four (4) snaps.

2. Use a screwdriver or coin to remove the two battery door screws and open the door.

3.Disconnect the front battery pack. Grip the white cord on the first front set of batteries and pull firmly to disconnect the connector from the battery compartment.

4. Pull the front battery out of the UPS by pulling the clear label, not the white cord. The white cord is connected to the battery leads, not the body of the battery.

5.Disconnect and remove the remaining battery packs by repeating steps 2 and 3.

Notes:

Be careful removing the batteries - they are heavy. Support the bottom of the batteries as

you remove them.

The 5000 VA model has two stacked sets of batteries. Exercise special care when removing

the top set.

6.Replace the back battery pack. For rack mount units, hold a battery pack so its battery leads

are on the right-hand side and slide it into the UPS. For tower units, hold the battery such that the battery leads are on the top and slide it into the UPS. Push the battery pack to the back of the compartment.

7.Reconnect the battery pack by pressing the gray connector into the plug at the right-hand side (rack mount units) or top (tower units) of the battery housing.

Note:

Small sparks at the battery connectors are normal during connection.

8.Repeat steps 6 and 7 for the remaining battery packs.

9.Close the battery door, replace the screws, and replace the front cover.

Batteries must be recycled. Deliver the battery to an appropriate recycling facility or ship it to the supplier in the new battery’s packing material. See the instructions included with the new battery for more information.

990-7032A, Revision 3 7/01

10

Image 16
Contents 990-7032A, Revision 3 7/01 990-7032A, Revision 3 7/01 Electrical Safety Handling SafetyReplacement and Recycling of Batteries Page Table of Contents Page Contents How to Unpack the UPSIntroduction UnpackingInstallation PlacementInstalling Rack Mount Units Position the UPSInstall the Mounting Rails in the Rack Hardwire the Electrical Connection Load the UPS into the RackInstall the Batteries Connect Power and Equipment to the UPSConnect Power to the UPS Install PowerChute and AccessoriesInitial Startup Low Battery Warning Interval Operating Instructions Storage Replacing the Battery User Configuration Items How to Determine On-Battery Run TimeUPS battery life differs based on usage and environment Tower and 5U Rack Mount 5000 VA ModelsSpecifications Regulatory Agency Approvals Troubleshooting Service Limited WarrantyIf the UPS requires service do not return it to the dealer APC Contact InformationRacks Rack Type Hole Type Hardware Required Hardware IncludedAppendix B Transporting Your Smart-UPS