American Power Conversion 2200 VA Factory User Selectable Function Default Choices Description

Page 10

Configuration

 

 

Factory

User Selectable

 

 

 

Function

 

Default

Choices

 

Description

 

 

 

 

 

 

 

Low Battery

 

2 minutes

Brightly

 

The low-battery warning beeps are continuous

Warning

 

 

illuminated:

when two minutes of run time remain.

PowerChute

 

 

low battery warning

To change the default interval setting, use a

software interface

 

 

level of about

2 minutes

pointed object such as a pen to press the

provides automatic,

 

 

Dimly illuminated:

VOLTAGE SENSITIVIY switch

(rear

unattended

 

 

low battery

shutdown when

 

 

panel), while

 

 

 

 

warning level of about

 

 

approximately two

 

 

 

 

 

 

 

5 minutes

 

 

 

 

minutes of battery

 

 

 

pressing the

button, (front display).

 

 

No illumination:

operated run time

 

 

 

 

Change the low battery warning interval setting

remains.

 

 

low battery warning

 

 

to the time that the operating system or system

 

 

 

level is about 8 minutes

 

 

 

software requires to safely shut down.

 

 

 

 

 

 

 

 

 

 

Synchronized

0 seconds

• 0 s

• 240 s

Specify the time the UPS will wait after the

Turn-on Delay

 

 

• 60 s

• 300 s

return of utility power before start up, (to avoid

 

 

 

• 120 s

• 360 s

branch circuit overload).

 

 

 

 

• 180 s

• 420 s

 

 

 

 

 

 

 

 

 

High Transfer Point

120

V models:

• 127 VAC

• 133 VAC

To avoid unnecessary use of the battery where

 

127

VAC

• 130 VAC

• 136 VAC

utility voltage is chronically high, set the high

 

 

 

 

 

transfer point higher if the connected

 

230

V models:

• 253 VAC

• 261 VAC

equipment can tolerate this condition.

 

 

 

 

 

253

VAC

• 257 VAC

• 265 VAC

 

 

 

 

 

 

 

 

 

Low Transfer Point

120

V models:

• 97 VAC

• 103 VAC

To avoid unnecessary use of the battery where

 

106

VAC

• 100 VAC

• 106 VAC

utility voltage is chronically low, set the low

 

 

 

 

 

transfer point lower if the connected equipment

 

230

V models:

• 196 VAC

• 204 VAC

can tolerate this condition.

 

 

 

 

 

 

208 VAC

• 200 VAC

• 208 VAC

 

 

 

 

 

 

 

 

 

Output Voltage

 

 

 

 

230 V models only: Sets the output voltage of

230 V models

230

VAC

• 220 VAC

• 240 VAC

the UPS.

 

 

 

 

 

 

 

 

 

 

10

Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual

Image 10
Contents APC Smart-UPSXL Page About this UPS SpecificationsIntroduction UnpackInstall the Rails in the Rack InstallationInstall the UPS in the Rack and Connect the Battery Module Start Up AccessoriesConnect Equipment and Power to the UPS Rear PanelsStart the UPS Emergency Power OffCommunication Ports Operation Display Panel Indicators and Function ButtonsDisplay Panels Feature Feature Title Function Button Configuration UPS settingsFactory User Selectable Function Default Choices Description Replacing the Battery Module Maintenance, Transport, and ServiceService Troubleshooting Problem and/or Possible Cause SolutionProblem and/or Possible Cause Solution There is no utility power Limited Warranty Regulatory and Warranty InformationRegulatory Agency Approvals and Radio Frequency Warnings Date of product declaration APC Worldwide Customer Support