Configuration
|
| Factory | User Selectable |
|
|
| |
Function |
| Default | Choices |
| Description |
| |
|
|
|
|
|
| ||
Low Battery |
| 2 minutes | Brightly |
| The | ||
Warning |
|
| illuminated: | when two minutes of run time remain. | |||
PowerChute |
|
| low battery warning | To change the default interval setting, use a | |||
software interface |
|
| level of about | 2 minutes | pointed object such as a pen to press the | ||
provides automatic, |
|
| Dimly illuminated: | VOLTAGE SENSITIVIY switch | (rear | ||
unattended |
|
| low battery | ||||
shutdown when |
|
| panel), while |
|
| ||
|
| warning level of about |
|
| |||
approximately two |
|
|
|
|
| ||
|
| 5 minutes |
|
|
|
| |
minutes of battery |
|
|
| pressing the | button, (front display). | ||
|
| No illumination: | |||||
operated run time |
|
| |||||
|
| Change the low battery warning interval setting | |||||
remains. |
|
| low battery warning | ||||
|
| to the time that the operating system or system | |||||
|
|
| level is about 8 minutes | ||||
|
|
| software requires to safely shut down. | ||||
|
|
|
|
| |||
|
|
|
|
| |||
Synchronized | 0 seconds | • 0 s | • 240 s | Specify the time the UPS will wait after the | |||
|
| • 60 s | • 300 s | return of utility power before start up, (to avoid | |||
|
|
| • 120 s | • 360 s | branch circuit overload). |
| |
|
|
| • 180 s | • 420 s |
|
|
|
|
|
|
|
|
| ||
High Transfer Point | 120 | V models: | • 127 VAC | • 133 VAC | To avoid unnecessary use of the battery where | ||
| 127 | VAC | • 130 VAC | • 136 VAC | utility voltage is chronically high, set the high | ||
|
|
|
|
| transfer point higher if the connected | ||
| 230 | V models: | • 253 VAC | • 261 VAC | equipment can tolerate this condition. | ||
|
|
|
| ||||
| 253 | VAC | • 257 VAC | • 265 VAC |
|
|
|
|
|
|
|
|
| ||
Low Transfer Point | 120 | V models: | • 97 VAC | • 103 VAC | To avoid unnecessary use of the battery where | ||
| 106 | VAC | • 100 VAC | • 106 VAC | utility voltage is chronically low, set the low | ||
|
|
|
|
| transfer point lower if the connected equipment | ||
| 230 | V models: | • 196 VAC | • 204 VAC | can tolerate this condition. |
| |
|
|
|
| ||||
| 208 VAC | • 200 VAC | • 208 VAC |
|
|
| |
|
|
|
|
|
| ||
Output Voltage |
|
|
|
| 230 V models only: Sets the output voltage of | ||
230 V models | 230 | VAC | • 220 VAC | • 240 VAC | the UPS. |
|
|
|
|
|
|
|
|
|
|
10 |