Troubleshooting

Problem and/or Possible Cause

Solution

There is no utility power

There is no utility power and the UPS is off.

Use the cold start feature to supply power to the connected equipment front the UPS battery(s).

Press and hold the button. There will be a short beep followed by a longer beep. Release the button during the second beep.

UPS operates on battery although line voltage exists

The UPS input circuit breaker trips.

Unplug all nonessential equipment from the UPS.

 

Reset the circuit breaker.

 

 

Your system is experiencing very high,

Move the UPS to a different outlet on a different circuit: Inexpensive fuel

low or distorted line voltage.

powered generators may distort the voltage. Test the input voltage with the

 

utility voltage display, (see Operation). If acceptable to the connected

 

equipment, reduce the UPS sensitivity.

 

 

Battery Charge and Load LEDs flash simultaneously

 

 

The UPS has shut down.

Check that the room temperature is within the specified limits for operation.

The internal temperature of the UPS has

Check that the UPS is properly installed, allowing for adequate ventilation.

exceeded the allowable threshold for

Allow the UPS to cool down. Restart the UPS. If the problem persists,

safe operation.

contact APC at www.apc.com.

 

 

Diagnostic utility voltage

 

 

 

All five LEDs are illuminated.

The line voltage is extremely high and should be checked by an electrician.

 

 

There is no LED illumination.

The line voltage is extremely low and should be checked by an electrician.

 

 

On Line LED

 

 

 

There is no LED illumination.

The UPS is running on battery, or it must be turned on.

 

 

The LED is blinking.

The UPS is running an internal self-test.

 

 

14

Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual

Image 14
Contents APC Smart-UPSXL Page About this UPS SpecificationsIntroduction UnpackInstall the UPS in the Rack and Connect the Battery Module InstallationInstall the Rails in the Rack Start Up AccessoriesConnect Equipment and Power to the UPS Rear PanelsCommunication Ports Emergency Power OffStart the UPS Display Panels Display Panel Indicators and Function ButtonsOperation Feature Feature Title Function Button Configuration UPS settingsFactory User Selectable Function Default Choices Description Service Maintenance, Transport, and ServiceReplacing the Battery Module Troubleshooting Problem and/or Possible Cause SolutionProblem and/or Possible Cause Solution There is no utility power Regulatory Agency Approvals and Radio Frequency Warnings Regulatory and Warranty InformationLimited Warranty Date of product declaration APC Worldwide Customer Support