American Power Conversion 3000 VA, 2200 VA user manual Configuration, UPS settings

Page 9

Configuration

Configuration

UPS settings

Settings are adjusted through PowerChute software or optional SmartSlot accessory cards.

Function

Factory

User Selectable

 

Description

Default

Choices

 

 

 

 

 

Automatic

On startup and

• Every 7 days

Set the interval at which the UPS will execute a

Self-Test

every 14 days

(168 hours)

 

self-test.

 

 

(336 hours)

• On startup and every

 

 

 

there after

14 days (336 hours)

 

 

 

 

there after

 

 

 

 

 

• On startup only

 

 

 

 

• No self-test

 

 

 

 

 

 

 

UPS ID

UPS_IDEN

Up to eight characters

Uniquely identify the UPS, (i.e. server name or

 

 

(alphanumeric)

location) for network management purposes.

 

 

 

 

 

Date of Last

Manufacture

mm/dd/yy

 

Reset this date when you replace the battery

Battery

Date

 

 

module.

 

Replacement

 

 

 

 

 

 

 

 

 

 

Minimum Capacity

0 percent

• 0%

• 60%

Specify the percentage to which batteries will

Before Return from

 

• 15%

• 75%

be charged following a low battery shutdown

Shutdown

 

• 30%

• 90%

before powering connected equipment.

 

 

• 45%

 

 

 

 

 

 

 

 

Voltage Sensitivity

High sensitivity

Brightly

 

Adjust by pressing the VOLTAGE SENSITIVIY

The UPS detects

 

illuminated: high

 

 

 

sensitivity

switch

(rear panel). Use a pointed object,

and reacts to line

 

voltage distortions

 

Dimly illuminated:

(such as a pen) to do so.

by transferring to

 

medium sensitivity

Note: In situations of poor power quality, the

battery operation to

 

No illumination:

UPS may frequently transfer to battery

protect the

 

low sensitivity

operation. If the connected equipment can

connected

 

 

 

operate normally under such conditions, reduce

equipment.

 

 

 

the sensitivity setting to conserve battery

 

 

 

 

capacity and service life.

 

 

 

 

Voltage sensitivity levels can be changed

 

 

 

 

through PowerChute software.

 

 

 

 

 

Alarm Delay

Enable

• Enable

 

Mute ongoing alarms or disable all alarms

Control

 

• Mute

 

permanently.

 

 

• Disable

 

 

 

 

 

 

 

 

Shutdown Delay

90 seconds

• 0 s

• 360 s

Set the interval between the time when the UPS

 

 

• 90 s

• 450 s

receives a shutdown command and actual

 

 

• 180 s

• 540 s

shutdown.

 

 

 

• 270 s

• 630 s

 

 

 

 

 

 

 

 

Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual

9

Image 9
Contents APC Smart-UPSXL Page Introduction SpecificationsAbout this UPS UnpackInstallation Install the Rails in the RackInstall the UPS in the Rack and Connect the Battery Module Connect Equipment and Power to the UPS AccessoriesStart Up Rear Panels Emergency Power Off Start the UPS Communication Ports Display Panel Indicators and Function Buttons OperationDisplay Panels Feature Feature Title Function Button UPS settings ConfigurationFactory User Selectable Function Default Choices Description Maintenance, Transport, and Service Replacing the Battery ModuleService Problem and/or Possible Cause Solution TroubleshootingProblem and/or Possible Cause Solution There is no utility power Regulatory and Warranty Information Limited WarrantyRegulatory Agency Approvals and Radio Frequency Warnings Date of product declaration APC Worldwide Customer Support