4.0 Installation

4.8 Input voltage tap selection—208 Vac, 50/60 Hz use only

As furnished, the UPS is configured to operate from a single phase

220–240 Vac, 50/60 Hz source. To operate the UPS from a 208 Vac, 50/60 Hz source, the UPS must be reconfigured. The steps required for this action are listed below. Note that regardless of the input voltage tap selected, the UPS’s output will remain in the 220–240 Vac range unless an alternate power distribution plate is installed.

4.8.1Turn off (O) the UPS’s input circuit breaker and unplug the input power cord.

4.8.2Remove the 10-32 x 3/8-in. SEM screw holding the red Input Voltage Select Wire (see illustration) to the tap bar marked “240 VAC SELECT.”

4.8.3Move the red Input Voltage Select Wire to the tap bar marked

“208 VAC SELECT” and tighten the screw.

4.8.4See Section 5.2.6 to check the UPS’s upper transfer to on-battery voltage and to set the UPSs output voltage reporting to “208 V.”

W

é x˜–

/￿/￿1

–é–z

— –

 

/ –¡0

 

 

 

 

208 VAC

240

VAC

SELECT

 

SELECT

 

 

 

 

/￿/￿1

 

 

 

 

208 VAC

240

VAC

SELECT

 

SELECT

 

 

 

 

220–240 Vac, 50/60 Hz

208 Vac, 50/6 Hz

input configuration

input configuration

21

Image 24
Contents Matrix UPS Important safety instructions Radio frequency interferenceLimited Warranty Life Support PolicyTable of Contents Introduction OverviewEmergency Power Off EPO Hot swappable modulesDisplay Remote interfacesSafety EnglishSécurité FrançaisSicherheit Vorsicht¡Seguridad ¡ATENCIONInput circuit breaker power on / OFF PresentationIsolation Unit IU Isolation Unit IUWiring inspection cover Power distribution plateEU separating screw Cx IEC 320 C13 receptaclesElectronics Unit EU Electronics Unit EUCooling fans Battery Pack coupler Accessory panelBattery communications jack Manual bypass switchBattery Pack Battery PackInput battery communications jack Output battery communications jackBattery Pack panel coupler Battery Pack cablesReplace Battery indicator In-line Battery Pack couplerInstallation Receiving inspectionProtection Strategies Moving the UPSPlacement Input voltage requirements 1 208 Vac operation2 220-240 Vac operation Installation procedures Required materialsInput hard wiring procedure Required toolsInstallation Typical input cable installation Input voltage tap selection-208 Vac, 50/60 Hz use only Output wiring procedure ¡- -y Zxyé Module interconnections Installation Emergency Power Off EPO interface Éx z¸ é ´´ éx z¸ÇxzÑ Xéé f Sgf j z¸Lgj Start-upOperation Modes of operationBypass mode Transfer between modes of operationDefault screens Display and controls operationMain menu screens UPS Control menu UPS Status menuUPS Diagnostics menu Operation UPS Setup Operation Operation Password protection UPS TestsPowerChute Software UPS MonitoringInterface Kits Computer Interface port Difficulty Difficulté Schwierigkeit VorsichtDificultad ¡ATENCIONPage Fault messages UPS requires serviceReplace Electronics Unit EU Replacing the Electronics Unit Replacing or adding Battery Packs UnitObtaining Service Storing the UPS Storage conditionsExtended storage Specifications Transfer CharacteristicsOutput Characteristics InputEnvironment PhysicalApprovals Page Recharge Time, Load Recharge Computer Declaration of Conformity Toll free technical support Return shipment addresses Serial Numbers

3000, 5000 specifications

American Power Conversion (APC) has long been a leader in the manufacturing of uninterruptible power supplies (UPS), and among its range of products, the APC 5000 and 3000 series stand out for their robust performance and reliability. These UPS systems are designed to ensure a continuous flow of power, protecting sensitive electronic equipment from fluctuations and outages.

The APC 5000 and 3000 models boast a range of key features that make them suitable for both commercial and residential applications. One of the primary characteristics is their high power capacity. The 5000 model provides a substantial 5000VA/4500W output, while the 3000 variant offers 3000VA/2700W. This enables users to connect multiple devices and critical loads without the risk of overload.

Both models utilize advanced double conversion technology, which ensures that the output power is consistently clean and stable. This technology is crucial for sensitive electronics, as it filters out voltage irregularities, providing pure sine wave output. This characteristic is particularly important for equipment like servers, data centers, and networking hardware, as it enhances their longevity and operational efficiency.

Another notable feature is their extended battery runtime capability. The APC 5000 and 3000 units are designed with hot-swappable batteries, allowing for easy replacement without interrupting the power supply. This enhances the overall reliability of the system, ensuring that even during maintenance, equipment remains operational.

In terms of connectivity, both models come equipped with multiple outlets for various plug types, as well as USB and network ports for monitoring and management. The integration with APC's PowerChute software allows users to manage power preferences, monitor battery health, and receive alerts when attention is needed. This level of monitoring is essential for facilities management teams, allowing them to ensure continuous operations without power-related disruptions.

The APC 5000 and 3000 also feature robust thermal management systems. With built-in fans, these units ensure efficient airflow and heat dissipation, protecting internal components from damage due to overheating.

In conclusion, the APC 5000 and 3000 series represent a powerful solution for those seeking reliable power protection. With their advanced technologies, multiple connectivity options, and serviceability features, these UPS systems stand out as trusted components in any power management strategy. Whether in a data center or a home office, the reliability and efficiency of these models make them invaluable in today’s power-dependent environment.