APC 1500XLJ, SURTA2200RMXL2U, 1500RMXL2U, 2200XL manual Emergency Power Off EPO, Connect the EPO

Page 10

Function

 

Factory Default

 

Options

Description

 

 

 

 

 

Low Bypass Points

100 Vac models

• 78 Vac

• 86 Vac

Minimum voltage that the UPS will pass to

 

78

Vac

• 80 Vac

• 88 Vac

connected equipment during internal bypass

 

 

 

• 82 Vac

• 90 Vac

operation.

 

 

 

• 84 Vac

• 92 Vac

 

 

 

 

 

 

 

120 Vac models

• 86 Vac

• 94 Vac

 

 

86

Vac

• 88 Vac

• 96 Vac

 

 

 

 

• 90 Vac

• 98 Vac

 

 

 

 

• 92 Vac

• 100 Vac

 

 

 

 

 

 

Output Frequency

Automatic selection

Automatic

 

Specify the UPS output frequency.

 

between:

50

± 0.1 Hz

 

Whenever possible the output frequency

 

50

± 3 Hz

50

± 3Hz

 

should track the input frequency.

 

60

± 3 Hz

60

± 0.1 Hz

 

 

 

 

 

60

± 3 Hz

 

 

 

 

 

 

 

Number of Battery

1

 

Number of connected battery

Defines the number of connected battery

Packs

 

 

packs

 

packs for proper runtime prediction.

1=internal battery module 2=one external battery pack 3=two external battery packs

Emergency Power Off (EPO)

The Emergency Power Off (EPO) option is a safety feature that will immediately remove power to all connected equipment. When EPO button is pushed, all connected equipment will immediately turn off and will not switch to battery power.

Adhere to all national and local electrical codes. Wiring must be performed by a qualified electrician.

The switch should be connected in a normally open switch contact. External voltage is not required; the switch is driven by 12 V internal supply. In closed condition, 2 mA of current are drawn.

The EPO switch is internally powered by the UPS for use with non-powered switch circuit breakers.

Connect the EPO

The EPO connector is located on the rear panel of the UPS.

1. Strip insulation from one end of each wire to be used for connecting EPO.

2.Insert a screwdriver into the slot above the terminal to be wired. Insert stripped wire into terminal. Remove screwdriver to secure wire in terminal. Repeat for each terminal.

The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect it only to other SELV circuits. The EPO interface monitors circuits that have no determined voltage potential. Such closure circuits may be provided by a switch or relay properly isolated from the utility. To avoid damage to the UPS, do not connect the EPO interface to any circuit other than a closure type circuit.

Use one of the following cable types to connect the UPS to the EPO switch.

CL2: Class 2 cable for general use.

CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.

CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.

CLEX: Limited use cable for use in dwellings and for use in raceways.

For installation in Canada: Use only CSA certified, type ELC, (extra-low voltage control cable).

For installation in other countries: Use standard low-voltage cable in accordance with national and local regulations.

8

SURTA 1500XL/1500XLJ/2200XL Series 100/120 Vac Tower/Rack-Mount 2U

Image 10
Contents Installation and Operation Page Smart-UPS Overview AccessoriesSafety InventoryFront display panel IndicatorProduct Overview DescriptionFront Display Panel Description Feature Rear panelRack-Mount and Stack Configurations InstallationSpecifications Tower ConfigurationOperation Connect the Internal Battery Install the BezelConnect Power and Start the UPS Connect equipment to the UPSUPS Settings ConfigurationFunction Factory Default Options Description Emergency Power Off EPO Connect the EPOTerminal Mode to Configure UPS Parameters Site Wiring Fault indicator is illuminated TroubleshootingUPS does not provide expected backup time UPS will not turn offBypass indicator is illuminated Battery Fault indicator is illuminatedFault indicator is illuminated Battery replacement Maintenance and TransportPrepare the UPS for transport Contact Information ServiceAPC Worldwide Customer Support Limited Warranty Two-Year WarrantyRadio Frequency Warning Vac models990-3622 2009