APC SURTA2200RMXL2U, 1500RMXL2U Troubleshooting, UPS will not turn off, UPS beeps occasionally

Page 12

Troubleshooting

Problem and Possible Cause

Solution

 

The UPS will not turn on or there is no output

 

 

The unit has not been turned on.

Press the ON button once to turn on the UPS.

 

 

The UPS is not connected to utility

Ensure that the power cable is securely connected to the utility power supply.

power.

 

 

 

The input circuit breaker has tripped.

Reduce the load to the UPS, disconnect nonessential equipment and reset the

 

circuit breaker.

 

 

The unit shows very low or no input

Check the utility power supply to the UPS by plugging in a table lamp. If the

utility voltage.

light is very dim, check the utility voltage.

 

 

The battery connectors are not

Ensure that all battery connections are secure.

securely connected.

 

 

 

The UPS will not turn off

 

 

 

The unit has not been turned off.

Press the OFF button once to turn off the UPS.

 

 

There is an internal UPS fault.

Do not attempt to use the UPS. Disconnect the UPS from utility and battery

 

power. Have the UPS serviced immediately.

 

 

UPS beeps occasionally

 

 

 

The UPS is in normal operation.

None. The UPS is protecting the connected equipment.

 

Press the ON button to silence the alarm.

 

The UPS is operating on battery, while connected to input utility power

 

 

The input circuit breaker has tripped.

Reduce the load to the UPS, disconnect nonessential equipment and reset the

 

circuit breaker.

 

 

There is very high, very low, or

Move the UPS to a different outlet on a different circuit. Test the input voltage

distorted input line voltage.

with the utility voltage display.

A connected generator is an inappropriate size.

XLJ models do not support the use of a generator.

Check the UPS and generator specifications for compatibility.

UPS does not provide expected backup time

The UPS battery is weak due to a recent outage or is near the end of its service life.

Charge the battery. Batteries require recharging after extended outages and wear out faster when put into service often or when operated at elevated temperatures. If the battery is near the end of its service life, consider replacing the battery even if the Replace Battery LED indicator is not yet illuminated.

A UPS overload condition has occurred. Check the UPS Load indicator. Disconnect nonessential equipment.

Site Wiring Fault indicator is illuminated

The UPS is connected to an improperly wired utility outlet.

Wiring faults detected include missing ground, hot-neutral polarity reversal and overloaded neutral circuit.

Do not attempt to use the UPS. Disconnect the UPS from utility and battery power. Contact a qualified electrician to correct the building wiring.

All indicators are off and the UPS is connected to utility service

The UPS has been shut down or the batteries are discharged from extended usage.

None. The UPS will restart automatically when utility power returns and configuration criteria have been met.

10

SURTA 1500XL/1500XLJ/2200XL Series 100/120 Vac Tower/Rack-Mount 2U

Image 12
Contents Installation and Operation Page Smart-UPS Accessories SafetyOverview InventoryIndicator Product OverviewFront display panel DescriptionFront Display Panel Description Feature Rear panelInstallation SpecificationsRack-Mount and Stack Configurations Tower ConfigurationConnect the Internal Battery Install the Bezel Connect Power and Start the UPSOperation Connect equipment to the UPSConfiguration UPS SettingsFunction Factory Default Options Description Emergency Power Off EPO Connect the EPOTerminal Mode to Configure UPS Parameters Troubleshooting UPS does not provide expected backup timeSite Wiring Fault indicator is illuminated UPS will not turn offBattery Fault indicator is illuminated Bypass indicator is illuminatedFault indicator is illuminated Maintenance and Transport Battery replacementPrepare the UPS for transport Service Contact InformationAPC Worldwide Customer Support Limited Warranty Two-Year WarrantyRadio Frequency Warning Vac models990-3622 2009