APC 2200XL, SURTA2200RMXL2U, 1500RMXL2U, 1500XLJ manual Terminal Mode to Configure UPS Parameters

Page 11

TERMINAL MODE TO

CONFIGURE UPS PARAMETERS

Terminal Mode is a menu driven interface that enables configuration of the UPS by users not wishing to use PowerChute® software or an optional Network Management Card.

Connect the serial cable to the serial com connector on the back of the UPS. If PowerChute software is not installed do not perform steps 1, 2, 8 and 9.

1.For Windows users: STOP the PowerChute Server using the following steps:

From the Desktop, go to Start => Settings => Control Panel => Administrative Tools => Services.

Select APC PowerChute Server - right click the mouse and select Stop.

2.For Linux users: STOP the PowerChute Server using the following steps:

Change directory to /etc/init.d.

Initiate the command ./PowerChute stop.

3.Open a terminal program. Example: HyperTerminal

From the Desktop, go to Start => Programs => Accessories => Communication =>HyperTerminal.

4.Double-click on the HyperTerminal icon.

Follow the prompts to choose a name and select an icon. Disregard the message, "...must install a modem," if it is displayed. Click OK.

Select the COM port that is connected to your UPS. The port settings are:

bits per second - 2400

data - bits 8

parity - none

stop bit - 1

flow control - none

Press ENTER

5.Press 1 to modify the UPS parameters.

6.Follow the prompts.

7.Exit the terminal program.

8.For Windows users: START the PowerChute Server using the following steps:

From the Desktop, go to Start => Settings => Control Panel => Administrative Tools => Services.

Select APC PowerChute Server - right click the mouse and select Start.

9.For Linux users: START the PowerChute Server using the following steps:

Change directory to /etc/init.d.

Initiate the command ./PowerChute start.

SURTA 1500XL/1500XLJ/2200XL Series 100/120 Vac Tower/Rack-Mount 2U

9

Image 11
Contents Installation and Operation Page Smart-UPS Inventory AccessoriesSafety OverviewDescription IndicatorProduct Overview Front display panelRear panel Front Display Panel Description FeatureTower Configuration InstallationSpecifications Rack-Mount and Stack ConfigurationsConnect equipment to the UPS Connect the Internal Battery Install the BezelConnect Power and Start the UPS OperationFunction Factory Default Options Description ConfigurationUPS Settings Connect the EPO Emergency Power Off EPOTerminal Mode to Configure UPS Parameters UPS will not turn off TroubleshootingUPS does not provide expected backup time Site Wiring Fault indicator is illuminatedFault indicator is illuminated Battery Fault indicator is illuminatedBypass indicator is illuminated Prepare the UPS for transport Maintenance and TransportBattery replacement APC Worldwide Customer Support ServiceContact Information Two-Year Warranty Limited WarrantyVac models Radio Frequency Warning990-3622 2009