APC 2200RMXL2U, 1500XL Configuration, UPS Settings, Function Factory Default Options Description

Page 9

Configuration

UPS Settings

Configure the settings using PowerChute software, a network management card or terminal mode.

Function

Factory Default

Options

Description

 

 

 

 

Automatic

On startup and every

• On startup and every

Set the interval at which the UPS will

Self-Test

14 days (336 hours)

7 days (168 hours)

execute self-tests.

 

there after

there after

 

 

 

 

• On startup and every 14

 

 

 

days

 

 

 

 

(336 hours) there after

 

 

 

• On startup only

 

 

 

• No self-test

 

 

 

 

 

 

UPS ID

UPS_IDEN

Use a maximum of eight

Uniquely identify the UPS, i.e. server name

 

 

alphanumeric characters to

or location for network management

 

 

define a name for the UPS.

purposes.

 

 

 

 

 

Date of Last

Manufacture

mm/dd/yy

 

Reset this date when the battery module is

Battery

Date

 

 

replaced.

Replacement

 

 

 

 

 

 

 

 

 

Minimum Capacity

0 percent

• 0%

• 60%

Specify the percentage to which batteries

Before Return from

 

• 15%

• 75%

will be charged following a low-battery

Shutdown

 

• 30%

• 90%

shutdown, before sending power to

 

 

 

 

connected equipment.

 

 

 

 

 

Alarm Delay

Enable

• Enable

• Disable

Specify the delay between an event and the

Control

 

• Mute

 

alarm to avoid alarms for insignificant

 

 

 

 

events.

 

 

 

 

 

Shutdown Delay

90 seconds

• 0 sec

• 360 sec

Specify the delay between the UPS

 

 

• 90 sec

• 450 sec

shutdown command and the actual

 

 

• 180 sec

• 540 sec

shutdown.

 

 

• 270 sec

• 630 sec

 

 

 

 

 

 

Duration of

2 minutes

• 2 min

• 14 min

Specify the number of minutes before

Low Battery

 

• 5 min

• 17 min

system shutdown, after the low battery

Warning

 

• 8 min

• 20 min

warning.

 

 

• 11 min

• 23 min

 

 

 

 

 

 

Synchronized

0 seconds

• 0 sec

• 240 sec

Specify the delay between the return of

Turn-on Delay

 

• 60 sec

• 300 sec

utility power and the UPS turns on. Set the

 

 

• 120 sec

• 360 sec

interval to avoid a branch circuit overload

 

 

• 180 sec

• 420 sec

condition.

 

 

 

 

 

High Bypass Points

100 Vac models

• 107 Vac

• 119 Vac

Maximum voltage that the UPS will pass to

 

110 Vac

• 110 Vac

• 122 Vac

connected equipment during internal bypass

 

 

• 113 Vac

• 125 Vac

operation.

 

 

• 116 Vac

• 128 Vac

 

 

 

 

 

 

 

120 Vac models

• 127 Vac

• 139 Vac

 

 

133 Vac

• 130 Vac

• 142 Vac

 

 

 

• 133 Vac

• 145 Vac

 

 

 

• 136 Vac

• 148 Vac

 

SURTA 1500XL/1500XLJ/2200XL Series 100/120 Vac Tower/Rack-Mount 2U

7

Image 9
Contents Installation and Operation Page Smart-UPS Safety AccessoriesOverview InventoryProduct Overview IndicatorFront display panel DescriptionRear panel Front Display Panel Description FeatureSpecifications InstallationRack-Mount and Stack Configurations Tower ConfigurationConnect Power and Start the UPS Connect the Internal Battery Install the BezelOperation Connect equipment to the UPSConfiguration UPS SettingsFunction Factory Default Options Description Connect the EPO Emergency Power Off EPOTerminal Mode to Configure UPS Parameters UPS does not provide expected backup time TroubleshootingSite Wiring Fault indicator is illuminated UPS will not turn offBattery Fault indicator is illuminated Bypass indicator is illuminatedFault indicator is illuminated Maintenance and Transport Battery replacementPrepare the UPS for transport Service Contact InformationAPC Worldwide Customer Support Two-Year Warranty Limited WarrantyVac models Radio Frequency Warning990-3622 2009