American Power Conversion 120-160kW manual Display will show invalid UPS data

Page 27

Alarms and Events

 

Alarms

Description

Action

 

 

 

 

23.

Main inverter failure

Temperature of main inverter, too

Check fan, check for airflow

 

 

high or inverter fuse blown

obstructions, check for overload,

 

 

 

check fuse

 

 

 

 

24.

High temperature of delta

Temperature of delta inverter, too

Check fan, check for airflow

 

inverter

high

obstructions, check for overload

 

 

 

 

25.

Low DC shutdown

Battery discharged to minimum

Ensure battery recharging

 

 

permissible level

 

 

 

 

 

26.

Low DC warning

Battery nearly discharged

Save your data now

 

 

 

 

27.

Mains momentarily outside

Short disturbances on mains

 

tolerance

supply (1 ms transients)

 

 

 

 

 

28.

Mains outside tolerance

Mains input voltage R.M.S. value

 

 

outside tolerance

 

 

 

 

 

29.

Mains frequency outside

Mains input frequency outside

 

tolerance

tolerance

 

 

 

 

 

30.

Bypass momentarily outside

Short disturbances on bypass

 

tolerance

voltage

 

 

 

 

 

31.

Bypass outside tolerance

Bypass input voltage outside

 

 

tolerance

 

 

 

 

 

32.

Bypass frequency outside

Bypass input frequency outside

 

tolerance

tolerance

 

 

 

 

 

33.

Output momentarily outside

Short disturbance on output

If message reappears -

 

tolerance

voltage (inrush current)

call for assistance

 

 

 

 

34.

Output outside tolerance

Output voltage outside tolerance

Call for assistance

 

 

 

 

35.

Output frequency outside

Output frequency outside

Call for assistance

 

tolerance

tolerance

 

 

 

 

 

36.

High battery temperature

Battery ambient temperature too

Check system ambient

 

 

high

temperature, check fan, check for

 

 

 

airflow obstructions

 

 

 

 

37.

Battery weak

Battery capacity below 75% or

Test battery capacity

 

 

battery MCCB/fuse switched off

 

 

 

 

 

38.

Battery defective

Insufficient battery capacity or

Call for assistance

 

 

battery MCCB/fuse switched off

 

 

 

 

 

39.

System locked in operation

UPS has made 10 attempts within

Unlock.

 

mode

1 minute to switch from bypass to

If message reappears -

 

 

battery operation, or “High DC

call for assistance

 

 

warning” has appeared 10-20

 

 

 

times within 1 minute

 

 

 

 

 

40.

RAM1 memory write error

UPS fault

Call for assistance

 

 

 

 

41.

Memory write error

UPS fault

Call for assistance

 

 

 

 

42.

Communication to VQ bypass

UPS fault

Call for assistance

 

lost

 

 

 

 

 

 

43.

Communication to VQ output

UPS fault

Call for assistance

 

lost

 

 

 

 

 

 

44.

Communication to DMU lost

UPS fault

Call for assistance

 

 

 

 

45.

Communication to controller

UPS fault.

Call for assistance

 

lost

Display will show invalid UPS data

 

 

 

 

 

990-4036

User Guide APC Silcon 120-160kW 400V UPS

27

Image 27
Contents Copyright 2000 APC Denmark ApS 120-160kW 400V UPS User GuideSafety Symbols used in this manual User Guide APC Silcon 120-160kW 400V UPSThank You Contents Introduction IntroductionDisplay Unit Start UPS from stand-by Stop/Start UPS and Operating the External Service BypassNormal operation Load power xx% Stop UPS for stand-bySwitching off the UPS Stop UPS for complete power downBlank UPS start-up Start UPS from complete power downDisplay shows System OFF Normal operation load power XX%Operating the External Service Bypass Switch single systems Bypassing the Single System UPSBypass operation Stop/Start UPS and Operating the External Service Bypass Bypass operation Normal operation Load power 0% System OFF Normal operation Load power 0% Bypass operationBypassing the Parallel UPS System All UPSs Acoustic alarm sounds for 30 secs Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Press the green on button on all systemsPress On the keyboard Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Operation OperationKeyboard Using the Remote Display Display of Measured ValuesBatt. load Batt. tank Economy Mode Parameter Settings Parameter SettingsParameter Settings Switching to Bypass Operation Programming KeysProgramming Example Load power xx% Mode Comments Alarms and EventsAlarms and Events Displaying the Alarm StackAlarms Description Action Possible AlarmsDisplay will show invalid UPS data Rectifying Alarm Messages Parallel Operation AlarmsCorrection of false alarm situations during service Battery Capacity Test Maintenance & TestingMaintenance & Testing Battery Monitoring TestTest Press Battery capacity TestUntil Test Xxx PressWarranty WarrantyAPC Silcon UPS Limited Factory Warranty APC Denmark How to Contact APCHow to Contact APC APC Corporate