American Power Conversion 120-160kW manual Parameter Settings

Page 22

Parameter Settings

4.0 Parameter Settings

Below tables show operating parameters programmable from keyboard. Only qualified users should alter programming parameters. See below examples.

Parameter Settings

Parameter

Setting*

 

Comments

 

 

 

 

 

 

 

Bypass operation

YES, NO

YES will switch the system into

 

 

bypass mode***

 

 

 

 

 

 

 

Language

GB, D, F, DK, S, SF, NL, PL, CZ,

Languages of text in display

 

E, P, SK, H

 

 

 

 

 

 

 

 

 

 

 

 

Autostart

YES, NO

Automatic restart by mains return

 

 

(1 min. delay). Ensures quick

 

 

battery recharge.

 

 

 

 

 

 

 

Remote shutdown active

YES, NO

Shutdown of UPS by remote

 

 

signal when in battery operation.

 

 

Saves battery energy.

 

 

 

 

 

 

 

Remote shutdown

HIGH, LOW

Nature of remote shutdown

 

 

signal level

 

 

 

 

 

 

 

 

 

Remote shutdown time

0, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10 min.

Time delay on remote shutdown

 

 

of UPS

 

 

 

 

 

 

 

 

 

Battery capacity test

Initiates back-up time check.

 

 

Time measured from start until it

 

 

reaches low DC warning level

 

 

(See User Guide, section 6).

 

 

 

 

 

 

Battery monitor test **

Initiates checks of battery

 

 

condition by 25% discharging.

 

 

 

 

 

 

Automatic battery test**

OFF, 3,6 months

Activates the battery monitor test

 

 

in cyclic intervals.

 

 

 

 

 

 

 

 

 

Battery monitor reset**

Press the

 

 

and

 

key to

 

 

reset alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

(flashing light).

 

 

 

 

 

 

 

 

 

Boost charge

YES, NO

YES results in boost charge (10

 

 

hours)

 

 

 

 

 

 

 

 

 

Autoboost charge

YES, NO

YES results in boost charge after

 

 

battery operation (10 hours).

 

 

 

 

 

 

 

Enter new date

YYMMDD

Set to local date

 

 

 

 

 

 

 

Enter new time

HHMMSS

Set to local time (24 hour clock)

 

 

 

 

 

 

 

 

*Factory settings in bold

**For systems with active Battery Monitor only

***Do not leave system running in bypass mode (Static bypass) for extended periods of time, as batteries are not recharged in bypass mode.

990-4036

22

User Guide APC Silcon 120-160kW 400V UPS

Image 22
Contents 120-160kW 400V UPS User Guide Copyright 2000 APC Denmark ApSUser Guide APC Silcon 120-160kW 400V UPS Safety Symbols used in this manualThank You Contents Introduction IntroductionDisplay Unit Stop UPS for stand-by Stop/Start UPS and Operating the External Service BypassNormal operation Load power xx% Start UPS from stand-byStop UPS for complete power down Switching off the UPSBlank Start UPS from complete power down UPS start-upSystem OFF Normal operation load power XX% Display showsBypassing the Single System UPS Operating the External Service Bypass Switch single systemsBypass operation Stop/Start UPS and Operating the External Service Bypass System OFF Normal operation Load power 0% Bypass operation Bypass operation Normal operation Load power 0%Bypassing the Parallel UPS System All UPSs Acoustic alarm sounds for 30 secs Stop/Start UPS and Operating the External Service Bypass Press the green on button on all systems Set input switches Q001 to positionPress On the keyboard Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Operation OperationKeyboard Display of Measured Values Using the Remote DisplayBatt. load Batt. tank Economy Mode Parameter Settings Parameter SettingsParameter Settings Programming Keys Switching to Bypass OperationProgramming Example Load power xx% Displaying the Alarm Stack Alarms and EventsAlarms and Events Mode CommentsPossible Alarms Alarms Description ActionDisplay will show invalid UPS data Parallel Operation Alarms Rectifying Alarm MessagesCorrection of false alarm situations during service Battery Monitoring Test Maintenance & TestingMaintenance & Testing Battery Capacity TestTest Xxx Press Battery capacity TestUntil Test PressWarranty WarrantyAPC Silcon UPS Limited Factory Warranty APC Corporate How to Contact APCHow to Contact APC APC Denmark