American Power Conversion 120-160kW manual Start UPS from complete power down, UPS start-up

Page 8

Stop/Start UPS and Operating the External Service Bypass

2.4Start UPS (from complete power down)

2.4.1 UPS start-up

CAUTION!

Make sure all cable connections are in place prior to first start-up.

Red / OFF

Green /ON

NOTICE!

After first system start-up, check that battery temperature is displayable (press and simultaneously on the display – it reads NV (not valid) if incorrectly installed). A battery capacity test is recommended after the electric installation.

NOTICE!

If for any reason the start-up procedure is interrupted, wait for the display to show the step 4 message: “Stop charge DC capacitors : YES” and repeat procedure from there.

CAUTION!

Do not close the MCCBs in the Battery Breaker Box unless the display reads: “Insert fuse or close MCCB” – otherwise the UPS may be damaged. If the display reads “DC capacitor charge error”, do not close MCCB.

Call for assistance.

WARNING!

If “Autostart” is active the UPS will start automatically after step 9 (with a 1-minute delay)

990-4036

8

User Guide APC Silcon 120-160kW 400V UPS

Image 8
Contents 120-160kW 400V UPS User Guide Copyright 2000 APC Denmark ApSThank You Safety Symbols used in this manualUser Guide APC Silcon 120-160kW 400V UPS Contents Display Unit IntroductionIntroduction Stop/Start UPS and Operating the External Service Bypass Normal operation Load power xx%Stop UPS for stand-by Start UPS from stand-byStop UPS for complete power down Switching off the UPSBlank Start UPS from complete power down UPS start-upSystem OFF Normal operation load power XX% Display showsBypass operation Operating the External Service Bypass Switch single systemsBypassing the Single System UPS Stop/Start UPS and Operating the External Service Bypass System OFF Normal operation Load power 0% Bypass operation Bypass operation Normal operation Load power 0%Bypassing the Parallel UPS System All UPSs Acoustic alarm sounds for 30 secs Stop/Start UPS and Operating the External Service Bypass Press On the keyboard Set input switches Q001 to positionPress the green on button on all systems Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Keyboard OperationOperation Batt. load Batt. tank Using the Remote DisplayDisplay of Measured Values Economy Mode Parameter Settings Parameter SettingsParameter Settings Programming Example Switching to Bypass OperationProgramming Keys Load power xx% Alarms and Events Alarms and EventsDisplaying the Alarm Stack Mode CommentsPossible Alarms Alarms Description ActionDisplay will show invalid UPS data Correction of false alarm situations during service Rectifying Alarm MessagesParallel Operation Alarms Maintenance & Testing Maintenance & TestingBattery Monitoring Test Battery Capacity TestBattery capacity Test UntilTest Xxx Press Test PressAPC Silcon UPS Limited Factory Warranty WarrantyWarranty How to Contact APC How to Contact APCAPC Corporate APC Denmark