American Power Conversion 120-160kW Alarms and Events, Displaying the Alarm Stack, Mode Comments

Page 25

Alarms and Events

5.0 Alarms and Events

Alarms are indicated by the red lamp (above the left hand corner of the keyboard) and a 30 seconds acoustic signal. An alarm is registered in the alarm stack as long as it is present, and if more in the same order as they arise.

Certain alarms, such as battery alarms, need resetting. See section 4.0 Parameter Settings.

All alarms are also registered in an event logger and remains there in a stack with room for 250 events. The events are stored in the same order as they arose - showing the latest first.

Besides the alarms the following operational modes are also stored in the event logger.

Mode

Comments

MPU is reset

UPS has been completely switched off

Stand-by

UPS has been in stand-by mode by parallel system

Normal operation

UPS has been in normal operation

Battery operation

UPS has been in battery operation

Bypass operation

UPS has been in bypass operation

System off

UPS has been off

5.1Displaying the Alarm Stack

Action

 

Description

1.

Press

 

Access to the alarm stack.

2.

Press

or

Scroll up or down through the alarm stack

 

 

 

messages.

 

 

 

Last message is "No (further) alarm".

3.

Press

 

Exits the alarm stack. If not operated the system

 

 

 

will exit the alarm stack automatically after 30

 

 

 

seconds.

 

 

 

 

5.2Displaying the Event Stack

Action

 

Description

1.

Press

and

Press the two keys simultaneously to get access

 

 

 

to the events stack

2.

Press

or

Scroll up or down through the event stack

 

 

 

(last message is "No (further) event").

3.

Press

 

Displays the time where the event happened.

4.

Press

 

Exits the event stack. If not operated the system

 

 

 

will exit the event stack automatically after 30

 

 

 

seconds.

 

 

 

 

990-4036

User Guide APC Silcon 120-160kW 400V UPS

25

Image 25
Contents Copyright 2000 APC Denmark ApS 120-160kW 400V UPS User GuideUser Guide APC Silcon 120-160kW 400V UPS Safety Symbols used in this manualThank You Contents Introduction IntroductionDisplay Unit Normal operation Load power xx% Stop/Start UPS and Operating the External Service BypassStop UPS for stand-by Start UPS from stand-bySwitching off the UPS Stop UPS for complete power downBlank UPS start-up Start UPS from complete power downDisplay shows System OFF Normal operation load power XX%Bypassing the Single System UPS Operating the External Service Bypass Switch single systemsBypass operation Stop/Start UPS and Operating the External Service Bypass Bypass operation Normal operation Load power 0% System OFF Normal operation Load power 0% Bypass operationBypassing the Parallel UPS System All UPSs Acoustic alarm sounds for 30 secs Stop/Start UPS and Operating the External Service Bypass Press the green on button on all systems Set input switches Q001 to positionPress On the keyboard Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Operation OperationKeyboard Display of Measured Values Using the Remote DisplayBatt. load Batt. tank Economy Mode Parameter Settings Parameter SettingsParameter Settings Programming Keys Switching to Bypass OperationProgramming Example Load power xx% Alarms and Events Alarms and EventsDisplaying the Alarm Stack Mode CommentsAlarms Description Action Possible AlarmsDisplay will show invalid UPS data Parallel Operation Alarms Rectifying Alarm MessagesCorrection of false alarm situations during service Maintenance & Testing Maintenance & TestingBattery Monitoring Test Battery Capacity TestUntil Battery capacity TestTest Xxx Press Test PressWarranty WarrantyAPC Silcon UPS Limited Factory Warranty How to Contact APC How to Contact APCAPC Corporate APC Denmark