UPS connections.

Note: UPS cables can enter through the top or the bottom of the MBP. However, BOTTOM is recommended.

Refer to the Smart-UPS VT 10-30kVA or MGE Galaxy 3500, 208V Installation Manual for MBP cable connections at the UPS.

1.Connect the four UPS inputs [L1, L2, L3, N, top-to-bottom] to the Q1 Switch in the MBP. Use a 4mm Allen wrench and torque to 60in-lbs [7Nm].

2.Connect the four UPS outputs [L1, L2, L3, N, top-to-bottom] to the Q2 Switch in the MBP. Use a 4mm Allen wrench and torque to 60in-lbs [7Nm].

3.Connect the two UPS control wires to Pins 7 and 8 in the MBP Control Terminal Block. Use a standard (flathead) screwdriver and make the screws hand-tight.

Control Wires [7, 8]

UPS Inputs to Q1

UPS Outputs to

 

Switch [L1, L2, L3, N]

Q2 Switch [L1, L2, L3, N]

12

Smart-UPS® VT and MGE™ Galaxy™ 3500 10-30 kVA 208 V MBP Installation

Image 16
Contents Installation Page Contents Page Safety Safety warningsLive maintenance precautions Features Product OverviewInternal components Schematic Considerations EnvironmentalInstallation OverviewTools Panel board breakersRemoving the front door optional  Mounting the MBP Internal cable connections Making external cable connections UPS connections Re-attaching the front door Installing Panel Board Breakers Removing fuses Appendix a Changing FusesReplacing fuses Page Page Page Page 990-4198D-001 2009