AMX manual NXA-UPS1500 Product Specifications

Page 6

NXA-UPS1500 Uninterruptible Power Supply

Product Specifications

NXA-UPS1500 Product Specifications

Input:

Voltage Window (DIP Switch selectable):

 

120V version (FG678-15): 110/115/120 Vac +35% ˜ -32%

 

240V version (FG678-20): 220/230/240 Vac +35% ˜ -32%

 

Frequency: 45 ˜ 65Hz (50/60Hz auto-sensing)

 

 

Output:

Voltage Window (AC Mode):

 

120V version (FG678-15): 110/115/120 Vac +8% ˜ -12%

 

240V version (FG678-20): 220/230/240 Vac +8% ˜ -12%

 

Voltage Window (INV Mode):

 

120V version (FG678-15): 110/115/120 Vac +/-5%

 

240V version (FG678-20): 220/230/240 Vac +/-5%

 

• Capacity (VA/W):1500/900

 

• Wave Form: Pure sine wave

 

• Frequency: 50Hz/60Hz +/-0.1Hz

 

• Transfer Time:2 ms typical

 

• Autonomy: > 8 min.

 

• DC Start: Yes

 

 

Battery:

• Type: 12V, sealed lead acid maintenance-free

 

• Capacity: 9AH

 

• Quantity: 4 12V batteries required

 

• Voltage:

 

120V version (FG678-15): 24 Vdc

 

240V version (FG678-20): 48 Vdc

 

• Recharge Time: 2 ˜ 4 hours to 90%

 

• Storage: Store at -15 to +30 °C (+5 to +86 °F), charge the UPS battery every 6

 

months / Store at +30 to +45 °C (+86 to +113 °F), charge the UPS battery every

 

3 months.

 

 

LED indicators:

• Utility mode

 

• Backup mode

 

• Battery conditions

 

 

Display LCD:

• Load level (%)

 

• Battery level (%)

 

• Bypass

 

AVR-Boost/AVR Buck

 

• Battery Low/Replace/Fault

 

• UPS Fault

 

• Site Wiring Fault

 

• Overload

 

 

Overload Protection:

• AC Mode: >110% Buzzer continuously alarms, and shuts down in 10 minutes.

 

• Inverter Mode: >120% Buzzer continuously alarms, and shuts down in 10

 

seconds.

 

 

Short Circuit Protection:

• AC Mode: Breaker and electronic circuit

 

• Inverter Mode: Shut down automatically in 8 cycles

 

 

Self-Diagnostics:

• Upon Power-on

 

 

Alarms:

• Line Failure

 

• Battery Low

 

• Overload and Fault

 

 

Operation Environment:

• Temperature: 32° - 104°F (0-40° C)

 

• Operation Humidity: 95% RH Maximum, non-condensing

 

 

 

 

 

2

NXA-UPS1500 Uninterruptible Power Supply

Image 6
Contents NXA-UPS1500 AMX Limited Warranty and Disclaimer Table of Contents Battery Replacement NXA-UPS1500 Uninterruptible Power Supply FeaturesOverview Product Specifications NXA-UPS1500 Product SpecificationsFront Panel LCD Other AMX EquipmentNXA-UPS1500 Uninterruptible Power Supply Important Notice Storage InstructionsImportant Safety Instructions Assembling the Battery Pack Accessing the Battery Compartment Step One Accessing the Battery Compartment Step TwoAccessing the Battery Compartment Step Three Page Place the UPS Properly Accessories for Tower and Rack MountMounting the NXA-UPS1500 UnpackingSelecting Installation Position UPS SetupTower Setup Tower Setup Step OneTower Setup Step Two Rack-Mount Setup Rack-Mount Setup Step OneRack-Mount Setup Step Two Rack-Mount Setup Step Three Rack-Mount Setup Step FourRack-Mount Setup Step Five Connecting the UPS Connect Utility and LoadConnect Network Surge Protection Connect the RS-232 Communication PortRS-232 Communication Port Pin Assignment NetLinxUPSConnecting the UPS NXA-UPS1500 Uninterruptible Power Supply Operation Operation Battery Replacement Assembling the Battery PackReplacing the UPS Battery Step One Replacing the UPS Battery Step Two Replacing the UPS Battery Step ThreeRecycling the Used Battery NXA-UPS1500 EPM Installation Important Safety InstructionsEPM Specifications Important NoticeEPM Installation and Operation Selecting Installation PositionUnpacking EPM Installation Instructions Tower Installation Step OneTower Installation Step Two Using the EPM With The UPS Use With UPS Step OneUse With UPS Step Two EPM Rack Mount Installation Rack Mount Installation Step OneRack Mount Installation Step Two Rack Mount Installation Step Three Rack Mount Installation Step FourConnecting the EPM To the UPS EPM Storage InstructionsReplacing the Battery In the EPM Replacing the Battery in the EPM Step OneReplacing the Battery in the EPM Step Two Replacing the Battery in the EPM Step Three Replacing the Battery in the EPM Step FourUPS Maintenance NXA-UPS1500 Uninterruptible Power Supply It’s Your World Take Control