8.3Anchor Bolts
Install the anchor bolts to secure the UPS on the floor. See Figure 8.2 for anchor bolt installation detail. Use 1/2” (12 mm) diameter anchor bolts. There are four 0.63” (16 mm) diameter holes provided in the cabinet base. See Figure 8.3A for the hole locations and dimensions for the specified Ancillary Cabinets..
Anchor Bolt
(1/2 in (12 MM))
4 x 0.63 in. (16 mm) diameter bolt holes
4 bolt holes (Side View)
FIGURE 8.2 ANCHOR BOLT INSTALLATION DETAIL
431A/431B | 431M |
4 x 0.63 in. Dia. (16 mm)
Back
Front
19.0 in. (483 mm)
4 x 0.63 in. Dia. (16 mm)
Back
26.7in.. (677 mm)
Front
11.0 in. (279 mm)
20.0in. (508 mm)
FIGURE 8.3A HOLE LOCATIONS/DIMENSIONS ON BOTTOM OF CABINETS
A
B
Dimensions A - 29 in. (736 mm) B - 60 in. (1523 mm) Use 4 ea. 3/8”x16 2 in long bolts to join adjacent UPS /ancillary cabinet frames. (The left side of each cabinet has a 3/8”x16 pin nut to receive the corresponding bolt.)
A
B
Left Side | Right Side |
FIGURE 8.3B HOLE LOCATIONS/DIMENSIONS ON SIDES OF CABINETS | |
|
|
4300 Series Ancillary Cabinets Installation and Operation Manual | 19 |