7 Storage/Operating Environment

7.1Storage Environment

Observe the following when storing the ancillary cabinets.

Store ancillary cabinet indoors.

Temperature fluctuations should be minimized.

The optimal storage temperature range is 68 – 77 °F (20 – 25° C).

A maximum temperature range of 32 – 104 °F (0 – 40 °C) should be observed.

The optimal relative humidity at the storage location should be between 50 – 60%.

Humidity must not exceed 90%.

Avoid locations where ancillary cabinet may be exposed to corrosive gas.

Avoid locations with dirt and/or dust.

TABLE 7.1 - UPS STORAGE/OPERATING ENVIRONMENT STANDARDS

Item

Environment standard

 

Storage Location

Indoors

 

Ambient Temperature

Minimum storage temperature: 32 °F (0 °C)

Maximum storage temperature: 104 °F (40 °C)

Relative Humidity

The relative humidity must be between 30 and 90% and without

condensation due to temperature changes.

 

 

This equipment is rated for installations up to 3240 ft. (1000 m)

Altitude

above sea level. Consult with the factory to determine the derating

 

factor for installations above 3240 ft. (1000 m).

Dust

Dust must not exceed normal atmospheric levels and must not

include conductive/corrosive particles, silicone or oils.

 

 

No flammable and/or explosive gas.

 

Hydrogen sulfide (H2S)

Less than or equal to 0.0001 PPM

 

Sulfurous acid gas (SO2)

Less than or equal to 0.05 PPM

 

Chlorine gas (Cl2)

Less than or equal to 0.002 PPM

Flammable Gas

 

 

Ammonia gas (NH3)

Less than or equal to 0.1 PPM

 

Nitrous acid gas (NO2)

Less than or equal to 0.02 PPM

 

Nitrous oxides (NOx)

Less than or equal to 0.02 PPM

 

Ozone (O3)

Less than or equal to 0.002 PPM

 

Hydrochloric acid mist (HCl)

Less than or equal to 0.1 mg/m3

7.2Operating Precautions

Initial startup/commissioning of the ancillary cabinet should be performed by factory authorized personnel.

1)The ancillary cabinet should not be powered up until the entire operation manual has been read. Follow Lockout/Tag Out procedures.

14

4300 Series Ancillary Cabinets Installation and Operation Manual

Image 22
Contents Series Ancillary Cabinets Page Series Product Use and Warranty Restrictions Qualified Personnel onlyUninterruptible Power System UPS Toshiba Customer Support Center PurposeToshiba Customer Support Center Toshiba International CorporationContents Toshiba Battery Cabinet w/ HX-205 431Bx000xxER111 11 431B Toshiba Battery Cabinet431M MBS Cabinet Installation Guide Introduction Symbols General Safety InstructionsProhibited Symbol indicates do not take action Signal Words Qualified PersonnelMaximum Operating Temperatures Important Safety InstructionsFactory Authorized Personnel Battery Safety Instructions Importantes Concernant LA SécuritéKeep the area around the UPS clean Safety PrecautionsGeneral Maintenance DisclaimerTransporting Avoid vibration or shock exceeding 0.5 gTransporting By Forklift Transporting by ForkliftInspection/Storage Install the ancillary cabinet in a controlled environment Installation PrecautionsKeep the Specified Clearance around the UPS Metal Conduit is not AN Acceptable Ground Conductor Routing and GroundingConnect only one 1 ground wire to the earth ground terminal Wiring/ConnectionPerform wiring and connections with correct polarity Follow the torque criteria for tightening screwsPage Storage/Operating Environment Operating PrecautionsStorage Environment Page Qualified Personnel only Maintenance PrecautionsQualified Personnel shall Installation Keep the Specified Clearance around the ancillary cabinetsUnpacking UPS ClearanceAnchor Bolts 431A/431B 431MGrounding Wire Example UPS Ground Bus4300 Series System Assembly Series Overview4300 UPS 431B Batt. Cabinet Optional10 431A Toshiba Auxiliary Cabinet 431A431A Assembled All cabinets are O’Brien Black TexturedAlternative Configurations Auxiliary Cabinet Warning Labels431A with 431M and 4300 UPS Bolt Tightening Specifications Torque431A with the 4300 UPS Compression Fittings431A Input/Output Power Cable Sizes OutputAnchor the 431A Cabinet 431A Base Anchor Points431A Join the Auxiliary Cabinet with the UPSSeries UPS 431M Join the 431A Cabinet with the 431MSeries Toshiba Auxiliary Cabinet Outline Drawing 431B Door Closed 11 431B Toshiba Battery Cabinet431B Door Open 11.1 431B Estimated Runtimes 43784 4030841750 480824431B and 4300 UPS Go to Section Place the 431B Cabinet 431B Power Cable Sizes Place the 431B CabinetJoin the Battery Cabinet with the UPS 431B Cable Access PlateComponent Wire the Battery Cabinet to the UPSSeries UPS 431B 11.7 431B Backup Runtime Tables 431B Factory Supplied Shunt Trip WiringToshiba Battery Cabinet Outline Drawing 431B300017ER111, 4318500008ER111 Toshiba Battery Cabinet w/ HX-205 431Bx000xxER11112 431B Door Closed 431B Door Open Battery Cabinet Mccb Detail 12.1 431B Estimated Runtimes69883 41750 Installation Safety Instruction Sizes Lug Tightening Torque Recommended/Maximum Wire size and Torque RequirementBattery Cab 127 Adc 150 aJoin the Battery Cabinet with the UPS Wire the Battery Cabinet to the UPS 12.7 431Bx000xxER111 Backup Runtime Tables 431B Typical Runtimes versus LoadToshiba Battery Cabinet HX-205 Schematic 10 Toshiba Battery Cabinet Outline Drawing 13.1 431M Maintenance Bypass Switch MBS Options 13 431M MBS Cabinet Installation Guide431M Door Closed 431M Door Open 431M Internal Arrangement 431M Cabinet Warning Labels Qualified Personnel only 431M Input/Output Power Cable Sizes 431M with 431A and 4300 UPSSuggested Nema 2-Hole Compression Fittings Locations/Dimension on UPS Base Upper Attach Points similar Place the 431M CabinetJoin the 431M Cabinet with the UPS PCB MBS Operation MBS Mechanical Interlock Plate Operation431M Cabinet Outline Drawing 14 431A MBS/PDU Distribution Purpose4400 MBS/PDU with Front Panels Installed Loto Lock-Out Tag-Out HaspInstalling 4310-30/50-KP-A Optional Kickplate InstallationBox Contents Tools RequiredInsert Side Plate tabs into F/B Plate slots Slide Side Plates in along C-Channel baseAlign the F/B Plate with the UPS front Attach the rear F/B Plate to the back of the UPSCompletion Move Side Plates to outer-most Channel base Installing 4310-30/50-KP-BInstall the F/B Plates Side Kick Plate Plate F/B Kick Plates Back Side SimilarDimensional Data External Layouts/DimensionsElectrical Conduit Knock-out Data Page Page Industrial Division