No. | Part |
4Battery Retention Strap
5MCCB - Battery Cabinet Breaker
+MCCB Positive Lug, Battery Cabinet DC Out
–MCCB Negative Lug, Battery Cabinet DC Out
6Access for Battery Cabi- net Output Lugs
7Anderson Connectors for Battery String Discon- nect (1 set per shelf)
(All cabinets are O’Brien Black (Textured))
5
7
+
–
6
4
Figure 12.2 Battery Cabinet MCCB Detail
12.1431B Estimated Runtimes
TABLE 12.1 431B ESTIMATED RUNTIMES
Battery Cabinet | UPS Rat- | DC Bus Nominal | Batteries/Circuit Breaker | Battery Runtime in Min. | |
Part Number* | ing | Voltage | Configuration | @ Full Load, 0.8 PF | |
431B30017ER111 | 30 kVA | 288 VDC | 1 Breaker, 1 Battery String | 017 | – 17 min. runtime |
|
|
|
|
|
|
431B30008ER111 | 50 kVA | 288 VDC | 1 Breaker, 1 Battery String | 008 | – 8 min. runtime |
12.2EQUIPMENT WARNING LABELS
DO NOT attempt to install, operate, maintain or dispose of this equipment until you have read and under- stood all of the product warnings and user directions that are contained in this instruction manual.
FIgure 12-2 shows examples of warning labels that may be found attached to the equipment. DO NOT remove or cover any of the labels. If the labels are damaged or if additional labels are required, contact your TOSHIBA representative for additional labels.
The following are examples of the warning labels that may be found on the equipment. The labels are there to provide useful information or to indicate an imminently hazardous situation that may result in seri- ous injury, severe property and equipment damage, or death if the instructions are not followed.
4300 Series Ancillary Cabinets Installation and Operation Manual | 41 |