1.Run the
2.Plug the shunt trip cable connector into the shunt trip receptacle in the lower left front of the UPS. (The connectors are keyed to only plug in one way.)
3.Reinstall the dead fronts.
Figure 11-7 - 431B Factory Supplied
Shunt Trip Wiring
11.7431B Backup Runtime Tables
The following give the typical backup runtimes at various loads for a single cabinet 431B.
UPS | Capacity | PF |
|
|
| Runtime in Minutes at % Full Load |
|
|
| ||||
|
|
| 100% | 90% | 80% | 70% | 60% | 50% | 40% |
| 30% | 20% | 10% |
4300 | 30kVA | 0.8 | 17 | 21 | 24 | 30 | 38 | 45 | 59 |
| >90 | >90 | >90 |
4300 | 30kVA | 0.9 | 15 | 17 | 20 | 24 | 33 | 38 | 53 |
| 74 | >90 | >90 |
4300 | 50kVA | 0.8 | 8 | 9 | 11 | 14 | 17 | 24 | 32 |
| 46 | 70 | >90 |
4300 | 50kVA | 0.9 | 7 | 8 | 9 | 11 | 15 | 20 | 26 |
| 44 | 60 | >90 |