*80

 

*81

SYSTEM NON-ALARM CODES

 

 

 

 

 

 

Enter 00-09; B-F (11-15).

 

 

 

 

Default = 00 for all reports

 

 

 

 

*80 1st Digit

*81 2nd Digit

1*20 EXIT ERROR LOGIC ENABLE

[0]

 

 

 

 

 

 

 

 

0=No; 1=Bypass E/E and Interior zones faulted after exit

delay.

 

 

 

Must be "0" for UL installations.

 

 

 

Close

Open

Low Battery

Low Battery Restore

AC Loss

AC Restore

Test

Power Up

Cancel

Program Tamper

*83 FIRST TEST REPORT TIME

 

1*21 EXIT DELAY RESET

[0]

 

 

 

 

 

 

 

 

0=No; 1=Resets Exit Delay to programmed value after zone is closed and then faulted prior to end of exit delay.

Must be "0" for UL installations.

FIELDS 122-125: Allow four sets of two zones each to be linked so that both must fault within a five minute period to cause an alarm. Default for these fields = [000], [000].

1*22

CROSS-ZONING PAIR ONE

 

 

 

 

 

1*23

CROSS-ZONING PAIR TWO

 

 

 

 

 

1*24

CROSS-ZONING PAIR THREE

 

 

 

 

 

1*25

CROSS-ZONING PAIR FOUR

 

MISCELLANEOUS WIRELESS OPTIONS

Fields 1*28 - 1*31 are not applicable for UL installations.

1*28 RF TX LOW BATTERY SOUND

[0]

1=immediate; 0=when disarmed

 

[Day 00; hour 12; min 00] Days 01-07 Hours 00-23 Min 00- 59; 00 in all boxes = instant (Day 01= Monday)

 

 

 

 

*84 SWINGER SUPPRESSION

[01]

 

 

 

 

 

01-15 alarms

Must be "00" (disabled) for UL.

*85 ENABLE DIALER REPORTS FOR PANICS & DURESS

1=enable; [0=disable]

995 996 999 Duress

*87

ENTRY WARNING

 

 

 

 

 

 

 

 

[1]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1=continuous; 0=3 beeps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*88

BURG. ALARM COMM. DELAY

 

 

 

 

[0]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1=16 seconds; 0=no delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Must be "0" for UL installations.

 

 

 

 

 

 

 

 

 

 

 

*89

RESTORE REPORT TIMING

 

 

 

 

[0]

 

 

 

 

 

 

 

 

 

 

 

 

 

0=Instant; 1=After bell timeout if zone is restored; 2=when

 

system is disarmed. Must be "0" for UL installations.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*90

SEC. SUBS. ACCT #

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter 00-09; B-F (11-15)

[15 15 15 15]

 

 

 

 

 

 

 

 

 

 

 

2nd Page Programming Fields (press *94)

 

 

 

 

 

 

 

 

1*01

 

 

1*09 ASSIGN RESPONSE TYPE FOR ZONES.

 

 

 

 

 

Skip these fields. Use #93 Menu Mode, Zone

 

 

 

Programming to program the response types.

1*17

 

LOBBY PARTITION

 

 

 

 

 

 

 

 

[0]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter the "common lobby" partition (1-8)

 

 

 

 

 

 

 

 

 

 

 

1*18

 

AFFECTS LOBBY

 

 

 

 

 

 

 

 

[0]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter 1 if this partition affects the common lobby;

enter 0 if it

 

 

 

does not.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Must be "0" for UL installations.

 

 

 

 

 

 

 

 

 

 

 

1*19

 

ARMS LOBBY

 

 

 

 

 

 

 

 

[0]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter 1 if arming this partition attempts to arm lobby; enter 0

 

 

 

if it does not.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Must be "0" for UL installations.

 

 

 

 

 

 

 

 

 

 

 

1*29

RF TX LOW BATTERY REPORTING

 

[0]

 

 

1=enable; 0=disable

 

 

 

 

 

 

 

 

 

 

1*30

RF RCVR CHECK-IN INTERVAL

[06]

 

 

02-15 times 2 hours; 00 disables supervision

 

 

 

 

 

 

 

 

 

1*31

RF XMITTER CHECK-IN INTERVAL

[12]

 

 

02-15 times 2 hours; 00 disables transmitter supervision

1*33

TOUCHTONE W/ROTARY BACKUP

 

[0]

 

 

 

 

1=enable; 0=disable

 

 

 

 

1*34

COMM. SPLIT REPORTING

 

[0]

 

 

 

0=no; 1=alarms and alarm restores primary, others secondary; 2=open/close, test secondary, others primary. See 751 for comments if using with dual reporting.

1*35 1*38 ALARM REPORT CODES & ID DIGITS FOR ZONES 65-80.

Skip these fields. Use #93 Menu Mode, Zone

Programming to program the report codes.

1*39 SUPERVISORY AND RESTORE CODES FOR ZONES 65-80.Enter 00-09; B-F (11-15).

Default = [00 00 00 00 00]

 

 

 

 

Alarm Rst

Trbl

 

Trbl Rst

 

Byp

 

Byp Rst