Zone Programming
If using 5800 Series transmitters, do not the install batteries until you are ready to enroll them. After enrolling the transmitter, the battery need not be removed. This is to prevent enrolling the wrong serial number.
PROMPTEXPLANATION
ZONE PROG? |
|
1 = YES 0 = NO | 0 |
Press 1 to enter ZONE PROGRAMMING mode. The following screens appear. Press [✱] to display the next screen. Press # to display a previous screen.
SET TO CONFIRM? |
|
1 = YES 0 = NO | 0 |
This prompt appears once upon entering Zone Programming Mode.
If “Yes,” Confirmation prompts will be displayed after the device’s Serial and Loop numbers have been entered later.
ENTER ZONE NO. |
|
00 = QUIT | 10 |
Zone 10 entered ↑
10 ZT P RC In L
0 0 | 1 | 1 0 | 0 0 1 |
10 ZONE TYPE
PERIMETER03
Zone number 10 and Zone Type 03 entry shown
†These are special zone types used with 5800 Series Wireless Pushbutton Units that result in arming the system in the STAY or AWAY mode, or disarming the system, depending on the selection made.
Enter the
System Supervisory Zones = 88, 89, 90, 91, 92 (duress), 97 and 98 (bell supervision) Keypad Panic Zones = 95, 96, 99
Press [✱] to continue.
This display appears, showing a summary of the zone's current programming. ZT = Zone Type, P = Partition, RC = Report Code, In = the input type of device, and L = the device's loop number to which the sensor is connected.
Some devices can support more than one zone by means of individual loops (for example, 5801, 5804, 5816, 5817, etc.). If the zone is not programmed, the display appears as shown here. If you are checking a zone's programming, and it is programmed satisfactorily, press [#] to back up one step and enter another zone number, if desired.
Press [✱] to continue.
Each zone must be assigned a zone type, which defines the way in which the system responds to faults in that zone. Refer to the Zone Type Definitions section in the ADEMCO
00 | = Assign for Unused Zones | 08 | = 24 Hr. Auxiliary | |
01 | = Entry/Exit #1, Burglary | 09 | = Fire Without Verification | |
02 | = Entry/Exit #2, Burglary | 10 | = Interior Delay, Burglary | |
03 | = Perimeter, Burglary | 20 | = | |
04 | = Interior Follower, Burglary | 21 | = Arm AWAY† | |
05 | = Trouble Day/Alarm Night | 22 | = Disarm† | |
06 | = 24 | Hr. Silent Alarm | 23 | = No Alarm Response |
07 | = 24 | Hr. Audible Alarm |
| (e.g., relay activation) |
Press [✱] to continue.
10 Partition
1
Enter the partition number
10 REPORT CODE |
|
1st 03 2nd 12 | 3C |
Enter the report code. The report code consists of 2 hexadecimal digits, each in turn consisting of 2 numerical digits. For example, for a report code of "3C," enter 03 for "3" and 12 for "C."
(Refer to the System Communication section in the Installation and Setup Guide for more information about report codes and reporting formats.)
Press [✱] to continue.
– 13 –