Honeywell Vista-50P/Vista-50PUL manual Relay commands

Models: Vista-50P/Vista-50PUL Ademco Vista Series Commercial Burglary Partitioned Security System With Scheduling

1 48
Download 48 pages 30.57 Kb
Page 44
Image 44
Relay commands:

Below is a list of the "Action" codes (desired actions) used when programming time-driven events. Note that these codes are independent of the "relay codes" programmed during the #93 Menu Mode–Relay Programming mode. If using Time Driven

Events, the following menu items must first be programmed using #93 Menu Mode - Relay Programming:

Enter Relay No.

(reference identification number)

Relay Group

(if applicable)

Restriction

 

Relay Type

(4204 or X-10)

Relay commands:

 

ECP Address

(4204)

Relay No.

(4204)

House Code

(X-10)

Unit Code

(X-10)

Action Specifier for commands 01-05 is Relay No.; Action Specifier for commands 06-10 is Relay Group No.

01 = Relay On

03 = Relay Close for 2 seconds

05 = Relay Close YY seconds (field 1*75)

07 = Relay Group Off

09 = Relay Group Close XX minutes (field 1*74)

02 = Relay Off

04 = Relay Close XX minutes (field 1*74)

06 = Relay Group On

08 = Relay Group Close for 2 seconds

10 = Relay Group Close YY seconds (field 1*75)

Arm/Disarm commands:

Action Specifier for commands 20-24 is Partition(s). Activation times 1 (Beginning), 2 (End), 3 (During) are the only valid choices for auto-arming and disarming functions.

20 = Arm-Stay

22 = Disarm

24 = Force Arm Away (Auto-bypass faulted zns)

Bypass commands:

21 = Arm Away

23 = Force Arm Stay (Auto-bypass faulted zns)

Action Specifier for commands 30-31 is Zone List #, Activation times 1 (Beginning), 2 (End), 3 (During) are the only valid choices for bypass commands.

30 = Auto bypass - Zone list

31 = Auto unbypass - Zone list

Open/Close Windows:

Action Specifier for commands 40-41 is Partition(s), and for 42 is Access Group. Activation time 3 (During) are the only valid choices for these commands.

40 = Enable Opening Window

41 = Enable Closing Window

42 = Enable Access Window

Activation time:

Refers to when the action is to take place relative to the time window.

1 = Beginning of time window

2 = End of time window

3 = During time window active period only (On at beginning of window, off at end). 4 = Beginning and end of time window

Limitation of Access Worksheet The system provides up to 8 Access Schedules that can be programmed for the system. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.

Acc

Mon

Tues

Wed

Thurs

Fri

 

Sat

Sun

Hol

Sch

W1

W2

W1

W2

W1

W2

W1

W2

W1

 

W2

W1

W2

W1

W2

W1

W2

1

2

3

4

5

6

7

8

— 44 —

Page 44
Image 44
Honeywell Vista-50P/Vista-50PUL manual Relay commands